TRACKER 220 SERIES
Digital Panel Indicators




                     A Complete Range of Universal Input Digital Panel Indicators
                                      for Temperature and Process Measurement
               CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                  Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
    TRACKER 220 SERIES INDICATORS
       Universal Input                                                 IP65 Front Panel
       Analogue Output                                                 Standard 1/8 DIN Size
       Digital Status Inputs                                           Red or Green LED Display
       Transmitter & Transducer Supplies                               Programmable Function Buttons
       Four Alarm Set points                                           Maths Functions
       Wide Ranging Power Input                                        Serial Communications

Universal Input                                                             Universal Power Input
Any one of over 20 different input types can be directly                 Wide-ranging 90 to 265v ac
connected. Thermocouple, RTD, 20mA, mV and 10 volt                          input allows world-wide
signals are accepted as standard.                                       installation. Low voltage ac/dc
                                                                             input option available.
Tough but Attractive                                                                                                      Connectivity
Designed to enhance the looks of any                                                                        Digital Status inputs, serial
instrument panel, the enclosure uses flame                                                                  communications, analogue
retardant (VO) materials and the front                                                                      output, transmitter supply,
panel conforms to IP65 (NEMA 4).                                                                               alarm relays, transducer
The plug in sleeve-type                                                                                        supply, are all available.
construction facilitates                                                                                           The instrument can
simple exchange                                                                                                          be removed for
for routine                                                                                                            routine servicing
servicing/calibration.                                                                                               without disturbing
                                                                                                                     these connections.
Clear Display
                                                                                                                 Front Panel Control
The flat, slightly recessed
                                                                                                         Full set-up is available using
display, together with
                                                                                                       the front panel buttons to step
high brightness red or
                                                                                                           through a simple password
green LEDs ensure
                                                                                                                protected menu. Some
maximum visibility even
                                                                                                       functions can be made directly
in difficult ambient
                                                                                                              available to an operator.
lighting conditions.
                                                                                                            Alternatively units can be
                                                                                                             supplied without buttons.




                                                    User Definable Buttons
                                           Two of the front panel buttons can be user
                                           programmed to provide one or more special
                                                   functions such as tare and
                                                           auto zero.



   CONFIGURATION                                                                                              SCADA
     SOFTWARE                                                                                                SOFTWARE
The Tracker 220 series of universal input indicators comprises a range of four models which offer unparalleled price and performance. The
use of surface mount components and modern microprocessor technology has enabled powerful features to be packed into a standard 1/8
DIN case. The measurement performance is significantly better than that normally associated with indicators in this price range.
The four models can be used for simple measurement-only applications or in more demanding situations requiring digital
communications, alarms, maths functions and complex signal conditioning. The powerful menu-driven software enables fast flexible
set-up from the front panel or via the serial communications interface. No adjustments of internal potentiometers, internal links or
plug-in cards are necessary.

                All Tracker 220 series indicators have been tested and comply with the European Electromagnetic Compatibility
                directives and safety requirements. The instruments are designed to be used in the most demanding applications and
                each carries the CE marking. The enclosure is manufactured in re-cyclable and flame-retardant (VO) materials and
                the front panel conforms to IP 65.
                                                           CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                                                               Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
         TRACKER 220 APPLICATIONS



Temperature                                                             Signal Re-Transmission
The Tracker 220 series can be used in a wide                            The user programmable isolated analogue output allows the
variety of temperature measurement applications with results            220 series to be used in applications where a local display as
displayed in °C, °F or Kelvin (Absolute). In applications               well as data recording is required. This output can be
where non-linearising temperature transmitters are used the             configured to transmit the measured, averaged, maximum or
Tracker 220 series can linearise the 4-20 mA signal received to         minimum value and has its own damping filter for noisy or fast
the thermocouple curve. Where accuracy is vital to an                   moving signals. The input can be locally conditioned and
application, a 220 series indicator can be calibration-matched          retransmitted over a relatively long distance. Being electrically
to the output of the actual sensor to be used, thus removing            isolated, problems associated with earth loops, which are often
most system measurement errors.                                         encountered in measurement systems, are eliminated.




Pressure and Weighing                                                   Communications
A variety of pressure transducers, pressure transmitters or strain      The Tracker 220 series serial protocol is compatible
gauge bridges can be connected to the Tracker 220 series. The           with most SCADA software packages. Up to 32 indicators can
indicator and sensor can be matched using the user calibration          be connected to a single master device in a multidrop two or
feature, greatly reducing errors due to sensor output and               four wire configuration. Tracker PC based software can be
excitation supply voltage variations. A front panel button or           supplied which enables multiple configurations to be modified
digital status input can be configured to provide an auto zero          and stored. The display and analogue output can be controlled
feature allowing zero offset errors to be eliminated. For weighing      via the serial interface, allowing an indicator to be used as a
applications, a tare function can be similarly configured.              remote display or control device.




Process Inputs                                                          Alarm and Control
The Tracker 220 series indicators have a number of features             The comprehensive alarm functions built into the Tracker 220
which make them particularly suitable for the measurement of            series make them particularly suitable for monitoring, switching
process signals. Maths functions allow calculations for orifice         and control applications.
plate, "V" notch weir flow and rectangular (Cippaletti) weir
flow. A filter is available for noisy or fast- moving signals. A 24     The hysteresis facility stops noisy signals switching alarms.
point user linearisation facility is provided for applications such     High and low deviation allow control around a setpoint. On
as tank contents measurements. All of the Tracker 220 input             and off delay times can be set, with individual alarms
types can be scaled to any engineering units within the display         configured as latching or non-latching, depending upon user
range or, if necessary, mapped to one of the thermosensor or            requirements. Alarms can be displayed or acknowledged on the
user linearisation curves. SG Correction is also available.             Tracker 220 front panel.

                      CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                          Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
                   TRACKER 220 SOFTWARE

All configuration parameters can be password protected and are preserved in the event of a power failure. The following
software functions are available to the user:

Input Type                                      Maths Functions                               Models 223 and 224 only
Linearisation Type                              Alarm Set-up x 4                              Status Input Set-up x 2
Internal or External CJC                        Averaging Time Period                         Transducer Supply Set-up
Sensor Break Detection                          User Linearisation                            Analogue Output Set-up
Display Resolution                              Password Set-up                               Analogue Output Scaling
Display Filter Time Constant                    Function Button Set-up x 2                    Analogue Output Damping
Scaling and Calibration                         Relay Set-up (222/224 only)                   Serial Comms Set-up


Advanced Maths                                                      Digital Status Inputs
All models have the following maths functions available to          Tracker models 223 and 224 are fitted with two digital inputs
the user:                                                           which can be activated by external volt-free contacts. These
                                                                    can be programmed individually by the user to perform one or
Maximum and Minimum (Peak/Valley) Memory                            more of the following functions:
Signal Averaging
Square Root                                                         Tare
5/2 Root                                                            Auto Zero
3/2 Root                                                            Display Hold
Tare (Weighing Applications)                                        Display Maximum
Auto Zero                                                           Display Minimum
S.G. Correction (Specific Gravity)                                  Display Average
The Auto Zero function is particularly useful for correcting        Reset Maximum, Minimum and Average
sensor zero offset errors in a system.                              Alarm Disable
                                                                    Alarm Acknowledge
                                                                    Analogue Output Hold
Software Alarms                                                     Keyboard Lock
                                                                    Display Test
There are four software alarms as standard on the Tracker 220
series indicators. A separate alarm menu is provided for each
alarm allowing for independent operation.
                                                                    Function Buttons
The software allows the user to configure the following             The two buttons marked        and     on the front panel of all
parameters for each alarm:                                          models can be user-programmed to give operator level access to
                                                                    one or more of the following functions:
Type (High, Low or Deviation)
Setpoint Value                                                      Tare
Deviation High and Low                                              Auto Zero
On and Off Delay Time                                               Display Hold
On and Off Hysteresis Value                                         Display Maximum
Output (None, Relay 1 or 2 or both)                                 Display Minimum
Latching or Non-Latching                                            Display Average
Alarm Display Message On or Off                                     Reset Maximum, Minimum and Average
Front Panel Setpoint Edit On/Off (Alarms 1 and 2)                   Display Test
Link Setpoint On or Off (Alarms 3 and 4)

The set-up link function allows multiple alarms to track one        Display
adjustable setpoint value.                                          The software allows the user to configure the display. The
                                                                    decimal point position can be set to the required measurement
All setpoint values can be password protected or Setpoints          resolution or switched to automatic (auto-ranging) mode. A
1 and 2 can be edited by an operator. The display can be set to     filter is available to damp fast-moving signals and leading zeros
flash a message when an alarm is active.                            can be suppressed if required.


Alarm Relay Control                                                 Password Protection
Models 222 and 224 are each fitted with two alarm relays which      The instrument's configuration can be protected by the use
can be activated by any of the four software alarms. In addition    of a user-definable password. In addition, editing of the alarm
the AND function allows a relay to be set only when two or          setpoints, alarm acknowledging and the resetting of the
more software alarms are active. Relays can be configured to be     maximum, minimum or average value memory can be
energised or de-energised (fail safe) in the alarm condition.       individually protected from an operator.


                           CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                               Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
                    TRACKER 220 FEATURES

                                                T/C       mA     V, mV




                                                RESISTANCE - R
                                                             TD




 Universal Input                                                         Analogue Output
 All of the Tracker 220 series can be directly connected                 Models 223 and 224 are fitted with an electrically isolated
 to most process sensors including thermocouples, RTDs,                  analogue output which has 0.05% resolution. This can be
 20mA loops, transmitters, or dc type signals. All                       configured by the user as 0-10 volt, 0-20 mA or 4-20 mA
 thermosensor ranges have built-in linearisation curves and              and can be scaled over any portion of the display range. For
 internal or external CJC is available. The display can                  example, a type K thermocouple can be retransmitted as a
 show °C, °F or Kelvin (Absolute), with the decimal point                linear 4-20 mA signal equivalent to 0-1000°C to another
 position being user-adjustable to give the required                     device such as a chart recorder or data logger. The output is
 measurement resolution or switched to automatic (auto                   linear to temperature (display value).
 ranging mode). The sensor break detection can be selected
 to produce upscale or downscale readings. Process inputs                The analogue output can be set to transmit the measured,
 can be scaled to any engineering unit and any input can be              the maximum, the minimum or the averaged value and has
 mapped to one of the thermosensor linearisation curves.                 its own damping filter for noisy or fast moving signals.




                                                                                                                   12345   12345




                                                BRIDGES       2 WIRE
                                                          TRANSMITTERS




Sensor Excitation                                                        Serial Communications
All Tracker 220 models are fitted with a fixed 24 volt DC                Both models 223 and 224 are fitted with an electrically-
output which is electrically isolated. This can be used to               isolated RS 422/485 serial interface. Models 221 and 222
power a single 20 mA loop for two wire transmitters.                     can optionally be fitted with two wire communications. All
                                                                         measured values and set-up parameters are accessible,
In addition the Tracker models 221 and 222 have a 10v                    however, the instruments can be set to be read only, thus
regulated supply and the Tracker models 223 and 224 are                  protecting their configuration.
fitted with a programmable 0-12 volt dc regulated output.
Both of these outputs are electrically isolated to 500v. The             Two protocols are available, namely the MODBUS and the
programmable supply is configured via the internal software              proprietary DTPI, which has been designed to be easier to
and is primarily designed to power strain gauge-type sensors             implement. The display, analogue output and transducer
including load cells.                                                    supply can all be set or configured via the serial interface.




                                                                                                                                   LO AD

                                                                                                                                   LO AD




User Linearisation                                                       Alarms
Some applications require a special linearisation curve to be            Each of the Tracker 220 series has four software alarms.
defined by the user. A typical example is tank contents                  These can be configured by the user for alarm type,
measurement where the pressure of a liquid can be measured               setpoint, on/off delay and on/off hysteresis value. Alarms
but this does not have a linear relationship to the actual               can be individually set to be latching or non-latching and
volume. User linearisation allows up to 24 calibration                   to flash a message on the front panel display when active.
points to be defined. Each point can be entered manually                 Any of the four software alarms can operate a relay (models
or, for greater accuracy, directly from the sensor output, thus          222 and 224 only). In addition a special AND function
removing most system measurement errors. The 24 readings                 allows a relay to switch only if two or more alarm
can be entered in any order. The Tracker 220 will use the                conditions are active. Relays can be configured to be
stored values to define the required linearisation curve.                energised or de-energised in the alarm condition.

                      CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                          Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
Display                                                                                         TRACKER 220 SELECTION CHART
Type: 14.2mm high brightness LED (red or green)                                                                                                   Accuracy including linearisation
Range: ­19999 to 99999 (T223, T224)                                         THERMOCOUPLES                             221 222 223 224             Worst case     Typical @ 25°C
       ­1999 to 9999 (T221, T222)                                           Type J Fe/NiCu          ­210 to 1200°C                                 ± 0.5°C            ± 0.2°C
Update Rate: 2 per second                                                   Type K NiCh/NiAl        ­270 to 1372°C                                 ± 0.5°C            ± 0.2°C
A/ D Converter                                                              Type T Cu/CuNi          ­270 to 400°C                                  ± 0.5°C            ± 0.2°C
Dual slope integrating with auto zero                                       Type B Pt30%/6%Rh       2220 to 1820°C                                 ± 1.5°C            ± 0.8°C
Conversion rate: 10 per second                                              Type E NiCh/CuNi        ­270 to 1000°C                                 ± 0.5°C            ± 0.3°C
Resolution: 16 bit + sign (1µV)
                                                                            Type N Nicrosil-Nisil   ­200 to 1300°C                                 ± 0.5°C            ± 0.3°C
Common mode Rejection: >150dB
                                                                            Type R Pt13%Rh Pt       2­50 to 1767°C                                 ± 1.0°C            ± 0.6°C
Series mode Rejection: >70dB (50 or 60Hz)
                                                                            Type S Pt10% ­Rh Pt     2­50 to 1767°C                                 ± 1.0°C            ± 0.6°C
Voltage Inputs
                                                                            Type U Cu/CuNi          ­200 to 400°C                                  ± 0.7°C            ± 0.4°C
Ranges: ± 100mV, ± 10V
                                                                            Type L Fe/Con           ­200 to 900°C                                  ± 0.7°C            ± 0.4°C
Accuracy: 0.05% of reading ± 20µV (typically 0.02%)
                                                                            Type G W/W26%Rh            0 to 2320°C                                 ± 1.0°C            ± 0.4°C
Resolution: 1µV (100mV range), 100µV (10V range)
Input Impedance (Ohms): >100M (mV i/p) >1M (V i/p)
                                                                            Type D W3%/26%Rh           0 to 2320°C                                 ± 1.0°C            ± 0.4°C
Current Input                                                               Type C W5%/26%Rh           0 to 2320°C                                 ± 1.0°C            ± 0.4°C
Range: ± 20mA                                                               Ni/Ni 18% Moly             0 to 1370°C                                 ± 1.0°C            ± 0.4°C
Accuracy: 0.05% of reading ± 4µA (Typically 0.02%)                          Platinel II                0 to 1370°C                                 ± 1.0°C            ± 0.4°C
Resolution: 2.0µA                                                           Palaplat                   0 to 240°C                                  ± 1.0°C            ± 0.4°C
Input Impedance: 5 Ohms typical
Maximum Burden: 100mV                                                       RESISTANCE THERMOMETERS
Reference Junction Compensation (CJC)                                       Pt100 (alpha=385)       ­200 to 850°C                                   ± 0.5°C              ± 0.2°C
Accuracy: better than ± 0.5°C after 30 minutes                              Pt100 (alpha=392)       ­100 to 457°C                                   ± 0.5°C              ± 0.2°C
Resistance/ RTD Inputs                                                      Pt130                   ­200 to 500°C                                   ± 0.5°C              ± 0.2°C
Configuration: 2, 3 or 4 wire programmable.                                 Ni 100                  2­60 to 250°C                                   ± 0.5°C              ± 0.2°C
Excitation Current: 0.25mA typical
Range: 0­400 Ohms (0-4K Ohms using 10V input)                               DC INPUT TYPES
Accuracy: 0.4 Ohms (typically 0.2 Ohms)                                     ± 20mA                                                                  ± 0.05%              ± 0.02%
Resolution: 0.01 Ohms                                                       ± 100mV                                                                 ± 0.05%              ± 0.02%
Thermosensor Break Detection                                                ± 10V                                                                   ± 0.05%              ± 0.02%
Programmable: Up or down scale
Transmitter / Transducer Supplies
                                                                            RESISTANCE 0­400 Ohms                                                   ± 0.4                ± 0.2
All supplies isolated: 500 Vdc/peak ac
                                                                            0­4000 Ohms using 10V Input                                             ± 0.5%               ± 0.3%
24V Transmitter supply ­ All models
Nominally 24V @ 32mA maximum                                                DISPLAY DIGITS                             4        4    5      5       Ordering Code
10V Regulated Transducer Supply ­ T221, T222                                °C, °F or KELVIN                                                
10 volts ± 0.1V @ 30mA maximum                                              USER LINEARISATION                                              
0­12V Regulated Transducer Supply ­ T223, T224                              DISPLAY FILTER                                                  
                                                                                                                                                    Model Number         Power Display
Resolution: 0.01V                                                           MATHS FUNCTIONS                                                 
Accuracy: ± 0.05V (Typically 0.02V)                                         MAX, MIN and AVERAGING                                                  Power
Temperature Drift: <100ppm/°C                                               INTERNAL OR EXTERNAL CJC                                                1  90 to 265V ac 50 or 60Hz
Output Ripple: <5mV                                                         2 x FUNCTION BUTTONS                                                       10VA (40mA @240V)
Output Current: 35mA maximum                                                4 x SOFTWARE ALARMS                                                     2  10 to 32V ac or dc.
Analogue Output ­ T223, T224                                                24V TRANSMITTER SUPPLY                                          
                                                                                                                                                    Display Colour
Isolation: 500 Vdc/peak ac                                                  10V TRANSDUCER SUPPLY                               
                                                                                                                                                    R Red
Ranges: User selectable 0­10V, 0­20mA or 4­20mA                             0­12V TRANSDUCER SUPPLY                                         
                                                                                                                                                    G Green
Accuracy: 0.2% of Span (typically 0.1%)                                     RS422/485 SERIAL INTERFACE                                      
Temperature drift: <100ppm/°C                                               DIGITAL STATUS INPUTS                                                   Example: 223­1­R
Output Ripple: <10mV                                                        TWO ALARM RELAYS                                                            Tracker 223, mains
Response: 63% within 32ms, 99% within 100ms                                 ANALOGUE OUTPUT                                                             powered with red display.
Resolution: 0.05% of Span (5mV or 0.01mA)
Maximum Voltage Output: 11V @ 22mA                                          Serial Communications                                   Physical/Mechanical
Maximum Current Output: 22mA @ 18V                                          Type: RS422/485 2 or 4 wire multidrop                   Front Panel: Protection to IP65 (NEMA4)
Load: 0-900 Ohms (mA)                                                       Speed: 1200, 2400, 4800 or 9600 baud                    Dimensions: 48mm (H) x 96mm (W) x 173mm (D)
Programmable damping filter                                                 Parity: Odd, even or none                               Panel Cutout: 44mm (H) x 92mm (W)
Alarm Relay Outputs ­ T222, T224                                            Stop Bits: 1 or 2                                       Depth Behind Panel: 166mm including terminals
Relays: 2 x Change over contacts ­ 1 Amp @ 250VAC                           Protocol: MODBUSTM (RTU or ASCII), J-BUS and DTPI       Weight: 0.4kg maximum. Packed weight 0.55kg.
                                 ­ 5 Amp @ 30VDC                            Isolation: 500 Vdc/peak ac
Safety and EMC Certifications                                                                                                       Environmental
Safety: EN61010, IEC1010. Susceptibility: EN50082­2, EN50082­1.                                                                     Temperature: 10­50°C operating, ­10 to 70°C storage.
Emissions: EN50081­1. CE Certified 1995, 1999                                                                                       Humidity: 0­95% RH non condensing
Specifications subject to change without notice. All trademarks acknowledged.