TRACKER 220 SERIES
Digital Panel Indicators
A Complete Range of Universal Input Digital Panel Indicators
for Temperature and Process Measurement
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
TRACKER 220 SERIES INDICATORS
Universal Input IP65 Front Panel
Analogue Output Standard 1/8 DIN Size
Digital Status Inputs Red or Green LED Display
Transmitter & Transducer Supplies Programmable Function Buttons
Four Alarm Set points Maths Functions
Wide Ranging Power Input Serial Communications
Universal Input Universal Power Input
Any one of over 20 different input types can be directly Wide-ranging 90 to 265v ac
connected. Thermocouple, RTD, 20mA, mV and 10 volt input allows world-wide
signals are accepted as standard. installation. Low voltage ac/dc
input option available.
Tough but Attractive Connectivity
Designed to enhance the looks of any Digital Status inputs, serial
instrument panel, the enclosure uses flame communications, analogue
retardant (VO) materials and the front output, transmitter supply,
panel conforms to IP65 (NEMA 4). alarm relays, transducer
The plug in sleeve-type supply, are all available.
construction facilitates The instrument can
simple exchange be removed for
for routine routine servicing
servicing/calibration. without disturbing
these connections.
Clear Display
Front Panel Control
The flat, slightly recessed
Full set-up is available using
display, together with
the front panel buttons to step
high brightness red or
through a simple password
green LEDs ensure
protected menu. Some
maximum visibility even
functions can be made directly
in difficult ambient
available to an operator.
lighting conditions.
Alternatively units can be
supplied without buttons.
User Definable Buttons
Two of the front panel buttons can be user
programmed to provide one or more special
functions such as tare and
auto zero.
CONFIGURATION SCADA
SOFTWARE SOFTWARE
The Tracker 220 series of universal input indicators comprises a range of four models which offer unparalleled price and performance. The
use of surface mount components and modern microprocessor technology has enabled powerful features to be packed into a standard 1/8
DIN case. The measurement performance is significantly better than that normally associated with indicators in this price range.
The four models can be used for simple measurement-only applications or in more demanding situations requiring digital
communications, alarms, maths functions and complex signal conditioning. The powerful menu-driven software enables fast flexible
set-up from the front panel or via the serial communications interface. No adjustments of internal potentiometers, internal links or
plug-in cards are necessary.
All Tracker 220 series indicators have been tested and comply with the European Electromagnetic Compatibility
directives and safety requirements. The instruments are designed to be used in the most demanding applications and
each carries the CE marking. The enclosure is manufactured in re-cyclable and flame-retardant (VO) materials and
the front panel conforms to IP 65.
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
TRACKER 220 APPLICATIONS
Temperature Signal Re-Transmission
The Tracker 220 series can be used in a wide The user programmable isolated analogue output allows the
variety of temperature measurement applications with results 220 series to be used in applications where a local display as
displayed in °C, °F or Kelvin (Absolute). In applications well as data recording is required. This output can be
where non-linearising temperature transmitters are used the configured to transmit the measured, averaged, maximum or
Tracker 220 series can linearise the 4-20 mA signal received to minimum value and has its own damping filter for noisy or fast
the thermocouple curve. Where accuracy is vital to an moving signals. The input can be locally conditioned and
application, a 220 series indicator can be calibration-matched retransmitted over a relatively long distance. Being electrically
to the output of the actual sensor to be used, thus removing isolated, problems associated with earth loops, which are often
most system measurement errors. encountered in measurement systems, are eliminated.
Pressure and Weighing Communications
A variety of pressure transducers, pressure transmitters or strain The Tracker 220 series serial protocol is compatible
gauge bridges can be connected to the Tracker 220 series. The with most SCADA software packages. Up to 32 indicators can
indicator and sensor can be matched using the user calibration be connected to a single master device in a multidrop two or
feature, greatly reducing errors due to sensor output and four wire configuration. Tracker PC based software can be
excitation supply voltage variations. A front panel button or supplied which enables multiple configurations to be modified
digital status input can be configured to provide an auto zero and stored. The display and analogue output can be controlled
feature allowing zero offset errors to be eliminated. For weighing via the serial interface, allowing an indicator to be used as a
applications, a tare function can be similarly configured. remote display or control device.
Process Inputs Alarm and Control
The Tracker 220 series indicators have a number of features The comprehensive alarm functions built into the Tracker 220
which make them particularly suitable for the measurement of series make them particularly suitable for monitoring, switching
process signals. Maths functions allow calculations for orifice and control applications.
plate, "V" notch weir flow and rectangular (Cippaletti) weir
flow. A filter is available for noisy or fast- moving signals. A 24 The hysteresis facility stops noisy signals switching alarms.
point user linearisation facility is provided for applications such High and low deviation allow control around a setpoint. On
as tank contents measurements. All of the Tracker 220 input and off delay times can be set, with individual alarms
types can be scaled to any engineering units within the display configured as latching or non-latching, depending upon user
range or, if necessary, mapped to one of the thermosensor or requirements. Alarms can be displayed or acknowledged on the
user linearisation curves. SG Correction is also available. Tracker 220 front panel.
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
TRACKER 220 SOFTWARE
All configuration parameters can be password protected and are preserved in the event of a power failure. The following
software functions are available to the user:
Input Type Maths Functions Models 223 and 224 only
Linearisation Type Alarm Set-up x 4 Status Input Set-up x 2
Internal or External CJC Averaging Time Period Transducer Supply Set-up
Sensor Break Detection User Linearisation Analogue Output Set-up
Display Resolution Password Set-up Analogue Output Scaling
Display Filter Time Constant Function Button Set-up x 2 Analogue Output Damping
Scaling and Calibration Relay Set-up (222/224 only) Serial Comms Set-up
Advanced Maths Digital Status Inputs
All models have the following maths functions available to Tracker models 223 and 224 are fitted with two digital inputs
the user: which can be activated by external volt-free contacts. These
can be programmed individually by the user to perform one or
Maximum and Minimum (Peak/Valley) Memory more of the following functions:
Signal Averaging
Square Root Tare
5/2 Root Auto Zero
3/2 Root Display Hold
Tare (Weighing Applications) Display Maximum
Auto Zero Display Minimum
S.G. Correction (Specific Gravity) Display Average
The Auto Zero function is particularly useful for correcting Reset Maximum, Minimum and Average
sensor zero offset errors in a system. Alarm Disable
Alarm Acknowledge
Analogue Output Hold
Software Alarms Keyboard Lock
Display Test
There are four software alarms as standard on the Tracker 220
series indicators. A separate alarm menu is provided for each
alarm allowing for independent operation.
Function Buttons
The software allows the user to configure the following The two buttons marked and on the front panel of all
parameters for each alarm: models can be user-programmed to give operator level access to
one or more of the following functions:
Type (High, Low or Deviation)
Setpoint Value Tare
Deviation High and Low Auto Zero
On and Off Delay Time Display Hold
On and Off Hysteresis Value Display Maximum
Output (None, Relay 1 or 2 or both) Display Minimum
Latching or Non-Latching Display Average
Alarm Display Message On or Off Reset Maximum, Minimum and Average
Front Panel Setpoint Edit On/Off (Alarms 1 and 2) Display Test
Link Setpoint On or Off (Alarms 3 and 4)
The set-up link function allows multiple alarms to track one Display
adjustable setpoint value. The software allows the user to configure the display. The
decimal point position can be set to the required measurement
All setpoint values can be password protected or Setpoints resolution or switched to automatic (auto-ranging) mode. A
1 and 2 can be edited by an operator. The display can be set to filter is available to damp fast-moving signals and leading zeros
flash a message when an alarm is active. can be suppressed if required.
Alarm Relay Control Password Protection
Models 222 and 224 are each fitted with two alarm relays which The instrument's configuration can be protected by the use
can be activated by any of the four software alarms. In addition of a user-definable password. In addition, editing of the alarm
the AND function allows a relay to be set only when two or setpoints, alarm acknowledging and the resetting of the
more software alarms are active. Relays can be configured to be maximum, minimum or average value memory can be
energised or de-energised (fail safe) in the alarm condition. individually protected from an operator.
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
TRACKER 220 FEATURES
T/C mA V, mV
RESISTANCE - R
TD
Universal Input Analogue Output
All of the Tracker 220 series can be directly connected Models 223 and 224 are fitted with an electrically isolated
to most process sensors including thermocouples, RTDs, analogue output which has 0.05% resolution. This can be
20mA loops, transmitters, or dc type signals. All configured by the user as 0-10 volt, 0-20 mA or 4-20 mA
thermosensor ranges have built-in linearisation curves and and can be scaled over any portion of the display range. For
internal or external CJC is available. The display can example, a type K thermocouple can be retransmitted as a
show °C, °F or Kelvin (Absolute), with the decimal point linear 4-20 mA signal equivalent to 0-1000°C to another
position being user-adjustable to give the required device such as a chart recorder or data logger. The output is
measurement resolution or switched to automatic (auto linear to temperature (display value).
ranging mode). The sensor break detection can be selected
to produce upscale or downscale readings. Process inputs The analogue output can be set to transmit the measured,
can be scaled to any engineering unit and any input can be the maximum, the minimum or the averaged value and has
mapped to one of the thermosensor linearisation curves. its own damping filter for noisy or fast moving signals.
12345 12345
BRIDGES 2 WIRE
TRANSMITTERS
Sensor Excitation Serial Communications
All Tracker 220 models are fitted with a fixed 24 volt DC Both models 223 and 224 are fitted with an electrically-
output which is electrically isolated. This can be used to isolated RS 422/485 serial interface. Models 221 and 222
power a single 20 mA loop for two wire transmitters. can optionally be fitted with two wire communications. All
measured values and set-up parameters are accessible,
In addition the Tracker models 221 and 222 have a 10v however, the instruments can be set to be read only, thus
regulated supply and the Tracker models 223 and 224 are protecting their configuration.
fitted with a programmable 0-12 volt dc regulated output.
Both of these outputs are electrically isolated to 500v. The Two protocols are available, namely the MODBUS and the
programmable supply is configured via the internal software proprietary DTPI, which has been designed to be easier to
and is primarily designed to power strain gauge-type sensors implement. The display, analogue output and transducer
including load cells. supply can all be set or configured via the serial interface.
LO AD
LO AD
User Linearisation Alarms
Some applications require a special linearisation curve to be Each of the Tracker 220 series has four software alarms.
defined by the user. A typical example is tank contents These can be configured by the user for alarm type,
measurement where the pressure of a liquid can be measured setpoint, on/off delay and on/off hysteresis value. Alarms
but this does not have a linear relationship to the actual can be individually set to be latching or non-latching and
volume. User linearisation allows up to 24 calibration to flash a message on the front panel display when active.
points to be defined. Each point can be entered manually Any of the four software alarms can operate a relay (models
or, for greater accuracy, directly from the sensor output, thus 222 and 224 only). In addition a special AND function
removing most system measurement errors. The 24 readings allows a relay to switch only if two or more alarm
can be entered in any order. The Tracker 220 will use the conditions are active. Relays can be configured to be
stored values to define the required linearisation curve. energised or de-energised in the alarm condition.
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
Display TRACKER 220 SELECTION CHART
Type: 14.2mm high brightness LED (red or green) Accuracy including linearisation
Range: 19999 to 99999 (T223, T224) THERMOCOUPLES 221 222 223 224 Worst case Typical @ 25°C
1999 to 9999 (T221, T222) Type J Fe/NiCu 210 to 1200°C ± 0.5°C ± 0.2°C
Update Rate: 2 per second Type K NiCh/NiAl 270 to 1372°C ± 0.5°C ± 0.2°C
A/ D Converter Type T Cu/CuNi 270 to 400°C ± 0.5°C ± 0.2°C
Dual slope integrating with auto zero Type B Pt30%/6%Rh 2220 to 1820°C ± 1.5°C ± 0.8°C
Conversion rate: 10 per second Type E NiCh/CuNi 270 to 1000°C ± 0.5°C ± 0.3°C
Resolution: 16 bit + sign (1µV)
Type N Nicrosil-Nisil 200 to 1300°C ± 0.5°C ± 0.3°C
Common mode Rejection: >150dB
Type R Pt13%Rh Pt 250 to 1767°C ± 1.0°C ± 0.6°C
Series mode Rejection: >70dB (50 or 60Hz)
Type S Pt10% Rh Pt 250 to 1767°C ± 1.0°C ± 0.6°C
Voltage Inputs
Type U Cu/CuNi 200 to 400°C ± 0.7°C ± 0.4°C
Ranges: ± 100mV, ± 10V
Type L Fe/Con 200 to 900°C ± 0.7°C ± 0.4°C
Accuracy: 0.05% of reading ± 20µV (typically 0.02%)
Type G W/W26%Rh 0 to 2320°C ± 1.0°C ± 0.4°C
Resolution: 1µV (100mV range), 100µV (10V range)
Input Impedance (Ohms): >100M (mV i/p) >1M (V i/p)
Type D W3%/26%Rh 0 to 2320°C ± 1.0°C ± 0.4°C
Current Input Type C W5%/26%Rh 0 to 2320°C ± 1.0°C ± 0.4°C
Range: ± 20mA Ni/Ni 18% Moly 0 to 1370°C ± 1.0°C ± 0.4°C
Accuracy: 0.05% of reading ± 4µA (Typically 0.02%) Platinel II 0 to 1370°C ± 1.0°C ± 0.4°C
Resolution: 2.0µA Palaplat 0 to 240°C ± 1.0°C ± 0.4°C
Input Impedance: 5 Ohms typical
Maximum Burden: 100mV RESISTANCE THERMOMETERS
Reference Junction Compensation (CJC) Pt100 (alpha=385) 200 to 850°C ± 0.5°C ± 0.2°C
Accuracy: better than ± 0.5°C after 30 minutes Pt100 (alpha=392) 100 to 457°C ± 0.5°C ± 0.2°C
Resistance/ RTD Inputs Pt130 200 to 500°C ± 0.5°C ± 0.2°C
Configuration: 2, 3 or 4 wire programmable. Ni 100 260 to 250°C ± 0.5°C ± 0.2°C
Excitation Current: 0.25mA typical
Range: 0400 Ohms (0-4K Ohms using 10V input) DC INPUT TYPES
Accuracy: 0.4 Ohms (typically 0.2 Ohms) ± 20mA ± 0.05% ± 0.02%
Resolution: 0.01 Ohms ± 100mV ± 0.05% ± 0.02%
Thermosensor Break Detection ± 10V ± 0.05% ± 0.02%
Programmable: Up or down scale
Transmitter / Transducer Supplies
RESISTANCE 0400 Ohms ± 0.4 ± 0.2
All supplies isolated: 500 Vdc/peak ac
04000 Ohms using 10V Input ± 0.5% ± 0.3%
24V Transmitter supply All models
Nominally 24V @ 32mA maximum DISPLAY DIGITS 4 4 5 5 Ordering Code
10V Regulated Transducer Supply T221, T222 °C, °F or KELVIN
10 volts ± 0.1V @ 30mA maximum USER LINEARISATION
012V Regulated Transducer Supply T223, T224 DISPLAY FILTER
Model Number Power Display
Resolution: 0.01V MATHS FUNCTIONS
Accuracy: ± 0.05V (Typically 0.02V) MAX, MIN and AVERAGING Power
Temperature Drift: <100ppm/°C INTERNAL OR EXTERNAL CJC 1 90 to 265V ac 50 or 60Hz
Output Ripple: <5mV 2 x FUNCTION BUTTONS 10VA (40mA @240V)
Output Current: 35mA maximum 4 x SOFTWARE ALARMS 2 10 to 32V ac or dc.
Analogue Output T223, T224 24V TRANSMITTER SUPPLY
Display Colour
Isolation: 500 Vdc/peak ac 10V TRANSDUCER SUPPLY
R Red
Ranges: User selectable 010V, 020mA or 420mA 012V TRANSDUCER SUPPLY
G Green
Accuracy: 0.2% of Span (typically 0.1%) RS422/485 SERIAL INTERFACE
Temperature drift: <100ppm/°C DIGITAL STATUS INPUTS Example: 2231R
Output Ripple: <10mV TWO ALARM RELAYS Tracker 223, mains
Response: 63% within 32ms, 99% within 100ms ANALOGUE OUTPUT powered with red display.
Resolution: 0.05% of Span (5mV or 0.01mA)
Maximum Voltage Output: 11V @ 22mA Serial Communications Physical/Mechanical
Maximum Current Output: 22mA @ 18V Type: RS422/485 2 or 4 wire multidrop Front Panel: Protection to IP65 (NEMA4)
Load: 0-900 Ohms (mA) Speed: 1200, 2400, 4800 or 9600 baud Dimensions: 48mm (H) x 96mm (W) x 173mm (D)
Programmable damping filter Parity: Odd, even or none Panel Cutout: 44mm (H) x 92mm (W)
Alarm Relay Outputs T222, T224 Stop Bits: 1 or 2 Depth Behind Panel: 166mm including terminals
Relays: 2 x Change over contacts 1 Amp @ 250VAC Protocol: MODBUSTM (RTU or ASCII), J-BUS and DTPI Weight: 0.4kg maximum. Packed weight 0.55kg.
5 Amp @ 30VDC Isolation: 500 Vdc/peak ac
Safety and EMC Certifications Environmental
Safety: EN61010, IEC1010. Susceptibility: EN500822, EN500821. Temperature: 1050°C operating, 10 to 70°C storage.
Emissions: EN500811. CE Certified 1995, 1999 Humidity: 095% RH non condensing
Specifications subject to change without notice. All trademarks acknowledged.