Hier Klicken für das PDF Dokument!!!

3200SERIES
ELECTRICAL TEST EQUIPMENT CALIBRATOR




                                                            Insulation Testers to 5kV     Ü
                                                            Portable Appliance Testers   Ü
                                                           Loop Testers                  Ü
 CompuMess Elektronik GmbH
   Lise-Meitner-Str.1, 85716 Unterschleissheim            RCD Testers                   Ü
      Tel 089-321501-0 Fax 089-321501-11
 http://www.compumess.de oder http://www.netzteile.de
                                                         Breakdown / Hipot Testers     Ü
                                                        Ground Bond Testers            Ü

 Ü          THE COMPLETE SOLUTION
            FOR ELECTRICAL TEST EQUIPMENT CALIBRATION
   3200 Electrical Test Equipment Calibrator - Five calibrators in one instrument · RCD, Insulationcalibrator for PATs · Loop
                                                                                  The worlds first
                                                                                                    & Breakdown Testers

  Insulation Testers                                 Resistance to 10GOhms                                             Test Voltage Measurement                                          Continuity Resistance & Current                               AC Voltage Output
   Providing all the functionality required                                   Continuously variable Insulation                                   Measures insulation test voltage &                                                                                             5 AC voltage outputs at
                                                                                                                                                                                                              3 ranges to 1kOhm (variable from
                                                                              resistance to 10GOhms @ 1kV.                                       current at nominal 1mA load for                                                                                                50V·100V·200V·230V·400V
   to calibrate all aspects of these popular                                                                                                                                                                  0.1Ohm to 20Ohms) and current
                                                                              Use the optional adaptor to check                                  16th edition equipment or 0.5mA                                                                                                for calibrating voltage ranges
   instruments.                                                                                                                                                                                               measurement to 320mA (@1Ohm)
                                                                              5kV testers with active guard.                                     for older equipment.

  PATs & Earth Bond Testers                          Earth Bond Resistance & Current                                   Insulation Resistance                                             Flash Voltage & Leakage Current                               Load Testing
   The 3200 is the quickest solution for
                                                                              10 precision resistance values with                                                                                             Class 1 & 2 flash voltage & current                               Open circuit, short circuit and
   calibrating all PAT functions. Also ideal                                  current measurement from 100mA to
                                                                                                                                                 Adjustable resistance to 10GOhms
                                                                                                                                                 - ideal for checking pass/fail levels                        measurement plus 3 AC leakage                                     0.13kVA load checks PAT
   for calibrating earth/ground bond testers                                  30A into 0.1 Ohms                                                                                                               ranges to 7mA                                                     operation / run tests
   with up to 30A test current.

  RCD Testers                                        RCD Current Measurement to 3A                                     RCD Trip Time 20ms to 5s                                          RCD Current Duration
   Simply plug in the RCD tester to the RCD                                   RMS and peak current measurements
                                                                                                                                                 Accurate & repeatable trip times                             The 3200 makes this normally difficult
                                                                              for all types of tester using digital
   test socket and start calibrating. The 3200                                                                                                   entered simply via the keyboard                              measurement straight forward with this
                                                                              waveform capture & analysis.
   will check and detect a faulty tester.                                                                                                        provide easy calibration.                                    dedicated function
                                                                              Graphical Indication of phase start

  LOOP Testers                                       Loop Resistance
   Calibrate these instruments quickly and
   safely. The auto loop options ensures
   accurate correction of the supply line
                                                                              10 precision resistance values
                                                                              incorporating line impedance - either
                                                                              entered directly or obtained using the
                                                                                                                            Ü       SOCKETS
   impedance.                                                                 auto loop measurement option                  Localised LOOP / RCD
                                                                                                                            Socket Options UK /
  Breakdown Testers                                  High Voltage Measurement to 12kV                                       EURO / Australian*
   External adapter for the calibration of                                    4 Voltage ranges : AC/DC 3kV & 12kV
                                                                              6 Current range : AC/DC 200uA, 2mA & 20mA
   Breakdown / hipot testers. Measures AC/DC                                  9 Load resistors for current measurements :
   voltage to 12kV and output current to 20mA                                 50kW (20mA) to 20MW (20uA) @ 1kV


   A Breakthrough In Electrical Test Equipment Calibration
    The increasing demand for the calibration of electricians tools brought on by government regulations
    and quality systems has presented a problem for calibration laboratories. Although these types of
    electrical equipment are relatively low in accuracy, they are difficult to calibrate due to the varied test
    equipment required, skill level and safety aspects associated with using live mains on an unprotected
    line. This precluded cost effective calibration...UNTIL NOW.                                                                                                   Ü          OPTIONAL ADAPTERS
    The 3200 revolutionises the process of calibration, providing a safe and controlled method to calibrate                                                         5kV INSULATION TESTER                       PORTABLE APPLIANCE                          BREAKDOWN / HIPOT
    these types of electrical instruments with a minimum level of training. Connect directly to a PC using                                                          ADAPTER FOR MEGGER                          TESTER FLASH                                TESTER ADAPTER

    Transmille's ProCal software via the built in RS232 interface (isolated for safety) to provide a turn-key                                                       INSULATION TESTERS                          TEST ADAPTER
                                                                                                                                *Other regions supported
    solution for automated calibration.                                                                                          using adapter lead



     Automate Calibration with ProCal - the easy to use calibration software                                                                                                                                    For a FREE evaluation CD contact our sales desk or visit
                                                                                                                                                                                                                www.transmille.com

                                                 Ü IMPROVED PRODUCTIVITY                                               Ü CALIBRATION PROCEDURES                                              Ü EXPAND FOR JOB CONTROL
                                                  ProCal software controls the calibrator and guides                   Procedures can be easily downloaded from a                            ProCal-Track provides an inventory & calibration
                                                  the user through a sequence of tests, recording                      library of procedures from www.transmille.com or                      management module to handle job control from
                                                  the results automatically ensuring fast, repeatable                  created using the integrated procedure builder                        goods-in to dispatch, and links seamlessly with
                                                  calibration that can be perfomed with a minimum                      wizard.                                                               ProCal.
                                                  of training.                                                                                                                               From single station to full network setups,
                                                                                                                                                                                             Transmille software is flexible to work the way you
                                                 Ü DOCUMENTATION OF RESULTS                                            Ü      THE COMPLETE SOLUTION                                          want to.
                                                  ProCal produces a selection of professionally                        ProCal provides the flexibility to grow for
                                                  formatted reports, including certificates and                        expanding requirements to support calibration of                      For further details see the Transmille
                                                                                                                       other types of instruments including DMMs, power                                                                                     · Intuitive graphical user interface
                                                  calibration labels - ideal for quality systems such
                                                                                                                       supplies, oscilloscopes - even pressure, torque &                       software brochure - click on to...
                                                  as ISO9000 and ISO17025. Custom reports can                                                                                                                                                               · Certificates printed directly on plain paper
Ü ULTRA PORTABLE SYSTEM                           also be written using Seagate Crystal Reports®.
                                                                                                                       dimensional disciplines.                                                      www.transmille.com                                     · Professional labels using dedicated label printer
   Ideal for on-site calibration
Ü 3200 Electrical Test Equipment Calibrator
  Continuity Testing                                                                  Pat Testing
                                                                                       Earth Bond Resistance
  Cont. Variable Range :              0.5W to 2kW (0.5W Resolution)
  Alternative Range (Option)     :    0.1 to 20 (0.01 Res.) ; 100W ; 1kW Fixed
                                                                                       Values                   :      See Loop Values
                                                                                       Accuracy                 :      0.5% ± 4mW
  Standard Accuracy      :            1% ± 25mW                                        Resolution               :      0.1mW (to 10W) : 1mW (to 1kW)
  High Accuracy (Option) :            0.25% ± 25mW
                                                                                       Earth Bond Current Measurements
  Continuity Current Measurement (Into 1)
                                                                                       Ranges                   :      100mA, 10A, 30A
  Range                          :    0 to 320mA (0.1mA Resolution)                    Resolution               :      1mA, 10mA, 10mA
  Accuracy                       :    1.3% ± 6 Counts                                  Accuracy                 :      1.5% ± 6 Counts

  Insulation Testing                                                                   PAT Insulation Resistance
  Range                          :    0 to 2GW (10GW Option : 5%)                      Range                    :      100kW to 1GW (10kW Resolution)
                                                                                       Accuracy                 :      See Insulation Resistance
  Accuracy                       :    10kW to 5MW 0.3% (0.1% Option)
                                      5MW to 2GW 3% (1% Option)
                                                                                       PAT Leakage
  Resolution                     :    10kW                                             Ranges                   :      2mA, 4.7mA, 7.7mA (1uA Resolution)
  Max Volt/Power                 :    1.1kV or 1 WATT (5kV Option)                     Accuracy                 :      1.5% ± 2 Counts
  Insulation Test Voltage Measurement
  Ranges                         :    50V, 100V, 250V, 500V, 1kV                       PAT Leakage Test Voltage
                                      (0.1V Resolution)                                Range                    :      100V to 300V RMS (0.1V Resolution)
  Current Measurement :               0.5mA, 1mA                                       Accuracy                 :      1.5% ± 9 Counts
  Accuracy            :               1% ± 8 Counts
  AC Voltage Output                                                                    Load Testing
                                                                                       Ranges                   :      S/C, O/C & 0.13kVA
  Range                          :    100V, 200V, 230V, 300V, 400V
                                                                                       Accuracy                 :      440W ± 5%
  Accuracy                       :    0.2% ± 1 Counts
                                                                                       Flash Testing (Option)
  RCD Testing                                                                          CLASS 1
  Time          Range            :    20ms to 5s (10ms Resolution)                     Range           :               1kV to 1.8kV (1V Resolution)
                Accuracy         :    ± 0.7ms                                          Load Resistance :               600kW (2.5mA @ 1.5kV)
  Current       Range            :    3mA to 3A                                        CLASS 2
                Resolution       :    0.01mA (to 200mA), 0.1mA (to 3A)                 Range           :               2kV to 3.6kV (1V Resolution)
                Accuracy         :    < 190ms 5% ± 20 Counts                           Load Resistance :               1.2MW (2.5mA @ 3kV)
                                 :    up to 5s 1.2% ± 6 Counts
                                                                                       Accuracy (Class 1&2) : 4% ± 10 Counts
  Timing Modes                   :    Immediate & Zero Crossing
  Current Modes                  :    I, ½ I, 2I, & 5I
                                                                                       Flash Current Measurement (Option)
  Display Modes                  :    0° and 180° Phase
                                                                                       Range          : 1mA to 3mA Resolution : 10uA
  LOOP Testing                                                                        Line Voltage Measurement
  Resistances
                                                                                       Range                    :      200V to 260V : 0.1V Resolution
  0.05W, 0.1W, 0.22W, 0.33W, 0.5W, 1W, 5W, 10W, 100W, 1kW                              Accuracy                 :      0.8% ± 6 Counts
  Resolution             : 0.1mW (to 10W) ; 1mW (to 1kW)
  Accuracy               : 0.5% ± 4mW                                                 General Specification
  Auto Loop (Option)
                                                                                       Line Power               :      230V/110V 50Hz /60Hz
  Maximum Correction             :    2W               Automatically                   Dimensions               :      45 x 44 x 14cm · Weight : 10kgs
  Resolution
  Accuracy
                                 :
                                 :
                                      100µW
                                      ±18mW      }      corrects for
                                                        supply loop
                                                                                       Warm-up Time             :      Double the time since last used
                                                                                                                       up to 20 minutes maximum.
  Measurement Current            :    4A                impedance.                     Interface                :      RS232

                         Ordering            Model 3200 Electrical test Equipment Calibrator      3200        Breakdown Tester Calibration Adapter              BREAKD
                         Information         High accuracy - improves resistance accuracy         HIACC       Low Range Continuity Option                       LOWR
                                             Extend insulation resistance to10GW                  10G         5kV Insulation Tester Adapter (for Megger BM11)   EXT5kV
                                             Automated loop (line-earth) measurement              AUTOL       Carry Case                                        CASE
                                             External PAT flash voltage measurement (up to 3kV)   FLASH       UKAS Certificate                                  3200UKAS

                                                                                                           AGENT
                                 UNIT 4 SELECT BUSINESS CENTRE,
                                 LODGE ROAD, STAPLEHURST, KENT.
                                 TN12 0QW. UNITED KINGDOM.
                                 TEL : +44 (0) 1580 890700                                                    CompuMess Elektronik GmbH
                                 FAX : +44 (0) 1580 890711                                                      Lise-Meitner-Str.1, 85716 Unterschleissheim
                                 EMAIL : sales@transmille.com                                                      Tel 089-321501-0 Fax 089-321501-11
                                                                                                             http://www.compumess.de oder http://www.netzteile.de
                                 WWW.TRANSMILLE.COM
                                                                                         0324
                           Due to continuous development specifications are subject to change
                           Windows is a registered trademark of Microsoft Corporation