Hier Klicken für das PDF Dokument!!!

                                                                                                                                            146-1941

     SERIES KBC
     BATTERY CHARGER
     The KBC is an updated and improved
     version of KEPCO's Series TBC battery
     charger. Along with several additional
     new features desired by battery charger
     users, it represents a new and innovative
     approach to battery charging. The KBC
     accomplishes the task of battery charging
     with a wide array of standard features,
     plus a unique blend of custom options
     that will appeal to just about every
     industrial battery user. To achieve this
     high level of flexibility KEPCO is
     combining microprocessor and switching
     power technologies. This combination
     allows us to offer flexibility along with
     excellent reliability and performance.
     The KBC product is uniquely capable
     of performing in any of the following              KBC MODEL TABLE
     applications, with any battery technology:
                                                                                 OUTPUT VOLTS       OUTPUT                 INPUT
     · Engine start                                          MODEL              NOMINAL RANGE      CURRENT     SIZE(2)     AMPS      EFFICIENCY COMMENTS

     · Fire pump control                                 KBC   12-3         12V      11.5-15V        3A          A        0.58A(1)    78%
     · Communications                                    KBC   12-7         12V      11.5-15V        7A          A        1.14A(1)    80%
     · Telecommunications                                KBC   12-10        12V      11.5-15V       10A          A        1.64A(1)    80%
     · CATV                                              KBC   12-20        12V      11.5-15V       20A          A        3.72A(1)    77%
     · Switchgear                                        KBC   12-40        12V      11.5-15V       40A          A        6.92A(1)    81%
     · Telemetry                                         KBC   12-100       12V      11.5-15V      100A          A       15.91A(1)    82%
     · Traction                                          KBC   24-3         24V       23-30V         3A          A        1.14A(1)    81%
     · Rail signaling                                    KBC   24-5         24V       23-30V         5A          A        1.63A(1)    82%
     · UPS side car charging                             KBC   24-12        24V       23-30V        12A          A        3.65A(1)    80%
                                                         KBC   24-20        24V       23-30V        20A          A        6.81A(1)    80%
     The heart of the KBC battery charger is its         KBC   24-50        24V       23-30V        50A          A        6.28A(3)    80%         (3)
     intelligent electronics that controls the           KBC   24-100       24V       23-30V       100A          B       12.73A(3)    82%         (3)

     entire system. This intelligence can be             KBC   48-2         48V       47-60V       2.5A          A        1.63A(1)    84%
     applied for use in creating additional battery      KBC   48-6         48V       47-60V         6A          A         3.6A(1)    81%
     charger and power board products. For               KBC   48-10        48V       47-60V        10A          A        6.46A(1)    84%
     example, we can use the same building               KBC   48-25        48V       47-60V        25A          A        6.21A(3)    80%         (3)

     blocks to offer a customized version of this        KBC   48-50        48V       47-60V        50A          B       15.09A(3)    80%         (3)

     product for hot swappable applications and        (1) Input current at 115V a-c.
     larger traction power uses. Further, KEPCO        (2) Size A--51/4 x 19 x 15 inches, 133 x 483 x 343 mm.
                                                           Size B--83/4 x 19 x 15 inches, 222 x 483 x 351 mm.
     is able to use this technology to develop a           Wall--15 x 19 x 83/4 inches, 381 x 483 x 222 mm.
     complete power board arrangement - designed       (3) AC Input 200-265V a-c, 47-66Hz, single phase only.
     to meet your specific application needs.
     KEPCO will provide custom charger designs
                                                        KBC GENERAL SPECIFICATIONS
     including the integration of DC-DC
     converters, DC­AC inverters, battery                       SPECIFICATION             RATING/DESCRIPTION
     disconnects, AC & DC                                Circuit Type                     Converter, switching type
     distribution, and custom                            Operating Temperature            -10 to +50°C without derating
     enclosures.
                                                         Storage Temperature              -30 to +75°C
                                                         Humidity                         10% - 95% RH non-condensing
                                                         Cooling                          Forced, with fan-stop sensor
                   AN ISO 9001 COMPANY
                                                         Output Noise                     <22dBrnC, voice band on battery
                                                         Output Filtering                 a) 30mVrms - when connected to a battery
                                                                                          whose AH rating is at least four times the
                                                                                          charger DC current rating
                                                                                          b) Without said battery, 12VDC - 250mVrms,
CompuMess 461-7000 · Fax: ·(718) 767-1102
  11352 USA · Tel: (718) Elektronik GmbH
   KEPCO, INC. · 131-38 Sanford Avenue Flushing, NY                                       24VDC - 300mVrms, 48VDC - 500mVrms

  Lise-Meitner-Str.1, 85716 Unterschleissheim
              Email: hq@kepcopower.com                   Battery Elimination              All chargers are fully capable of power supply
                                                                                          operation without a battery connected
     Tel 089-321501-0 Fax 089-321501-11
           www.kepcopower.com/kbc.htm
http://www.compumess.de oder http://www.netzteile.de
Standard Features for the KBC
                                                     TBC
                                                         ORDERING TABLE
                                                     KBC 12-20M 12V 11.5-15V             0-20A       A       115/230 4.6A(2)   77%
· Input
  - 86 ­ 265V a-c, 47 ­ 66Hz, single phase                     VOLTAGE   ­    CURRENT       A            B       C      D       E

  - 110-370V d-c (Safety agency approval             KBC                 ­
    does not apply for d-c input)
  - Active Power Factor Correction to                                    ­
    EN 61000-3-2
  - 400Hz operation
· AC protection using a multi-pole circuit
  breaker                                            KBC 12-20M
                                                         OPTIONS 12V 11.5-15V TABLE
                                                                 COMBINATION 0-20A
                                                     TBC                                             A       115/230 4.6A(2)   77%
· NEMA 1 enclosures for either 19" rack              OPTIONS                               DESCRIPTION
  mounted or wall mounted us
                                                       A        ALARMS & FORCED LOAD SHARE
· LED digital output metering                                   A) None
· LCD alphanumeric control/alarm indicator                      B) Forced load share with alarm (2 chargers in parallel)
                                                                C) Four additional assignable form C alarm contacts
· Sure-set on-line digital control for all set
                                                                D) Current limit alarm
  points, e.g. float voltage, equalize voltage,                 E) Alarm buzzer
  alarm thresholds, alarm relays, equalize                      F) B & C
  timer durations, and current limit                            G) B & C & D
· Alarm relays, 1 x form C user assignable                      H) B & C & D & E
                                                                 I) B & E
· High DCV alarm
                                                                J) C & E
· High DCV shutdown                                             K) D & E
· Low DCV alarm                                                 L) C & D
                                                                M) C & D & E
· Charger failure alarm
                                                       B         TEMPERATURE COMPENSATION
· Ground fault detection alarm, plus and
                                                                 A) None
  minus (May be disabled for grounded
                                                                 B) 25' probe
  systems)                                                       C) 50' probe
· Float/Equalize                                                 D) 100' probe
  - Automatic timer ­ priorities for AC                          E) 200' probe
    power failure &/or current limit
                                                       C        CUSTOM AC/DC PROTECTION
  - Auto-charge control
                                                                A) Standard
  - Manual equalize
                                                                B) ACCB, >/=25kAIC
  - Single rate operation                                       C) ACCB, >/=65kAIC
                                                                D) DC Fuse, 2 pole
Optional Features for the KBC                                   E) DCCB, >/=5kAIC
                                                                F) DCCB, >/=7kAIC
· Forced load share
                                                                G) DCCB, >/=10kAIC
· Failure of forced load share alarm                            H) B & D
· Temperature compensation                                       I) B & E
                                                                J) B & F
· Current limit alarm                                           K) B & G
· Communications                                                L) C & D
                                                                M) C & E
· Alarm buzzer                                                  N) C & F
· Drip proof enclosures                                         O) C & G
· Custom NEMA enclosures                               D         CUSTOM ENCLOSURES
· AC & DC custom circuit breakers/fuses                          A) Wall mounted
                                                                 B) 19" relay rack mounted
· Four additional assignable alarm form C                        C) Wall mounted NEMA 2 (drip proof)
  contacts                                                       D) Wall mounted NEMA 4/12 (spray proof, outdoor use)
· Multi-lingual operation
                                                       E         REMOTE COMMUNICATIONS PACKAGE
                                                                 A) Not included
             AN ISO 9001 COMPANY                                 B) Included




          CompuMess ·Elektronik Avenue · Flushing, NY 11352 USA · Tel: (718) 461-7000 · Fax: (718) 767-1102
             KEPCO, INC. 131-38 Sanford GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de