Hier Klicken für das PDF Dokument!!!
DC Power Supplies
By California Instruments KDC Series
· Compact DC Power
Uses less rack space compared to
other DC supplies of similar power
level.
· 5 to 15 KW & Beyond
Modular design supports
5, 10 and 15 kW versions.
Higher output using parallel opera-
tion of multiple chassis.
· Protection Modes
User selectable constant voltage trip
or constant current modes.
· Built-in Measurements
Voltage, current and power
readback capability standard.
· Transient Programming
User defined output sequence pro-
gramming from the front panel.
· Standard RS-232C Interface and
Optional GPIB.
Instrument drivers and software
support for easy system integration.
Compact Power Advanced Control Applications
The KDC Series packs up to 15 kW The KDC Series has three The advanced features and
of DC power in a 5.25" (3U) chassis. operational modes: constant capabilities of the KDC Series make
Despite the high power density of voltage, constant current and the power supply suitable for
the design, the KDC Series provides constant power. The constant challenging test applications such
a low noise, stable output. The DC voltage and constant current modes as: fuel testing, super capacitor
voltage ranges are 30 V to 600 Vdc, can be configured for voltage fold characterization, and other high
which supports a wide range of back or shutdown when the technology applications.
applications. programmed current limit set point The availability of RS-232, GPIB/
The KDC Series comes with an RS- is reached. IEEE-488, and isolated analog
232 as the standard remote The transient program function interfaces make the KDC easy to
programming interface. The IEEE- allows users to define up to 100 integrate into ATE and other
488/GPIB & isolated analog output sequences. Each sequence automated systems. The KDC
interfaces are optional. The KDC can contain up to six parameters. Series is designed to accept 208,
Series continuously measures Parameters include: voltage set 400 and 480V line-to-line AC inputs.
output voltage, current, peak point, slew rate, current set point,
current, and power. dwell time, and trigger. A graphical
user interface is included with each
KDC Series Power Supply. This
powerful interface software allows
users to generate automated test
routines in minutes. .
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11 · www.compumess.de · www.netzteile.de
KDC Series - Controller Capabilities
All KDC Series Power Supplies use an advanced DSP
based controller with a menu driven user interface. This
controller provides capabilities not typically found in
most DC supplies.
Output Sequencing: Time driven output changes can
be programmed, stored and executed under program
control. Events include steps, sweeps, drops and
surges of voltage and/or current. This allows a variety of
power conditions and DC tests to be set up and ex-
ecuted from the front panel. Multiple sequences can be
stored in nonvolatile memory for quick recall.
Parallel Mode: Multiple KDC units can be combined to
provide high output current capability using a master/
auxiliary combination.
Output Impedance: A programmable output impedance
function allows simulation of DC source impedance as a
function of load conditions. Graphical user interface DC supply control program.
Remote Control: The included KDC GUI program
provides easy access to these and other KDC controller
capabilities using a Windows PC with the standard RS-
232C or the optional IEEE-488/GPIB interface.
KDC Series - Models1
Output Output
Model Voltage C urrent R MS N oise Model Voltage C urrent R MS N oise
KD C 30-167 0-30 0-167 15mv KD C 150-33 0-150 0-33 25mv
KD C 30-333 0-30 0-333 15mv KD C 150-66 0-150 0-66 25mv
KD C 30-500 0-30 0-500 15mv KD C 150-100 0-150 0-100 25mv
KD C 40-125 0-40 0-125 15mv KD C 300-17 0-300 0-17 100mv
KD C 40-250 0-40 0-250 15mv KD C 300-33 0-300 0-33 100mv
KD C 40-375 0-40 0-375 15mv KD C 300-50 0-300 0-50 100mv
KD C 50-100 0-50 0-100 15mv KD C 400-12 0-400 0-12.5 100mv
KD C 50-200 0-50 0-200 15mv KD C 400-25 0-400 0-25 100mv
KD C 50-300 0-50 0-300 15mv KD C 400-37 0-400 0-37 100mv
KD C 80-62 0-80 0-62 25mv KD C 600-8 0-600 0-8 250mv
KD C 80-125 0-80 0-125 25mv KD C 600-17 0-600 0-17 250mv
KD C 80-187 0-80 0-187 25mv KD C 600-25 0-600 0-25 250mv
KD C 100-50 0-100 0-50 25mv
KD C 100-100 0-100 0-100 25mv
KD C 100-150 0-100 0-150 25mv
Note 1: Contact factory for availability of models with output voltage ranges not listed here.
KDC Series - Specifications
Electrical Protection
Output Over temperature, short circuit, over current protec-
tion, open sense.
Power
Maximum 5, 10 or 15 KW Controls and Indicator
Voltage
Controls
Line Regulation: < 0.1% of Range Dual digitally encoded rotary knobs, Function keys,
Load Regulation: < 0.1% of Range Output on/off, Power on/off
Accuracy: ± 0.05% Setting + 0.1% Range
Transient Response: Voltage will recover to within Indicators
2% of voltage range within 2 Display: Alphanumeric LCD, dual line.
msec for a 30 % load step. LED's for: Output on/off, CC mode, CV
Stability: ± 0.05% of max. rating per 8 mode, CP mode and Remote.
hours after 30 mins. warm-up
at fixed line, load and tempera- Remote Control
ture. A standard RS-232C is included with all KDC Series DC
Current Power Supplies. An optional GPIB/IEEE-488 with an
isolated analog interface is available as well.
Line Regulation: < 0.1% of Range
Load Regulation: < 0.1% of Range RS-232C / RS-485 - Standard
Accuracy: ± 0.05% Setting + 0.1% Range 9 pin D-shell connector, 115200 baud max., SCPI
Stability: ± 0.05% of setting after 8 hour syntax.
warm-up at fixed line, load and
-IF Option:
temperature.
IEEE-488 Interface
Input
IEEE-488 (GPIB) talker listener.
Voltage: 208 - 10 % to 230 +10% VAC
Subset: AH1, C0, DC1, DT1, L3, PP0,
400 ± 10 % VAC
RL2, SH1, SR1, T6
480 ± 10 % VAC
IEEE-488.2 SCPI syntax
All inputs are L-L, 3 phase, 3-
wire plus safety ground. Input Isolated Analog Interface:
rating must be specified at Voltage Control: 0-10 VDC, 0-5 VDC or R for 0-
time or order. 100% range
Current RMS: Typical RMS current per Current Control: 0-10 VDC, 0-5 VDC or R for 0-
phase at low line input voltage. 100% range
Power Level I/O Connectors: Analog I/O, 15 Pin D-sub,
Vlow 5 kW 10 kW 15 kW isolated
Auxiliary I/IO, 9 Pin D-sub, non-
187 V: 27 A 54 A 81 A
isolated
360 V: 15 A 30 A 45 A
Functions: Remote output on/off
432 V: 12 A 24 A 36 A Trigger input
Power Factor: > 0.65 Function strobe out
Volt monitor out
Efficiency: > 85 % at full load.
Current monitor out
Measurements
Voltage
Accuracy: 0.05% + 0.1% Full Scale
Resolution: 0.025% Full Scale
Current
Accuracy: 0.1% + 0.2% Full Scale
Resolution: 0.025% Full Scale
Power
Accuracy: 0.2% + 0.3% Full Scale
Resolution: 0.05% Full Scale
KDC Series - Specifications
Environmental Mechanical
Temperature Coefficient Dimensions
Voltage set point: 0.02%/°C of V Range Height: 5.25" / 133.35 mm
Current set point: 0.03%/°C of I Range Width: 19" / 482.6 mm
Ambient Temperature Depth: 22.19" / 563.3 mm excl. bus
bars and cover
Operating: 0° to 40° C / 32° to 104° F
24.74" / 628.4 mm incl. bus
Storage: -40° to 75° C / -40° to 167° F
bars and cover
Humidity
Weight 15 KW 10 KW 5KW
Operating: 0 to 80% RH, non condensing
Net: 84 lbs. 70 lbs. 56 lbs.
Cooling 38.1 Kg 32 Kg 25.4 Kg
Forced air, front intake, rear exhaust. Shipping (approx.): 110 lbs. 96 lbs. 82 lbs.
50 Kg 44 Kg 37.2 Kg
Rack Mounting
Unit must be supported by shelf or brackets when
mounted in 19" cabinet. No provisions for rack slides
are made on the instrument.
KDC Series - Ordering Information
Ordering Examples:
Ordering Information
Model Description
Model KDC 50-200-208 Output voltage 50 Vdc, maxi-
All KDC Series model numbers specify voltage and mum current is 200 Adc, line
current range. input is 208 V line to line, three
KDC VVV-CCC-LLL-XX. phase. Includes standard RS-
232C remote interface.
VVV = Voltage
KDC 80-187-400-IF Output voltage 80 Vdc, maxi-
CCC = Current
mum current is 187 Adc, line
LLL = Input Line Voltage input is 400 V line to line, three
XX = Options phase. Includes optional IEEE/
Refer to table shown for model numbers and configura- RS-232C and analog interfaces.
tions. XDS Series Products
Supplied with For applications requiring only basic controller functions
User manual and programming manual on CD ROM. but similar power levels and voltage ranges as the KDC
Series, refer to the Argantix XDS Series.
Windows GUI software on CD ROM.
RS-232C serial cable.
Options
-IF GPIB / IEEE-488 interface and analog
remote voltage programming option.
-400 400-440 Volt line to line, three phase AC
input option.
-480 432-528 Volt line to line, three phase AC
input option.
For more information call:
TEL: 858 404-6936 Email: sales@argantix.com © Copyright 2003, Argantix. San Diego, California, USA
Specifications subject to change without notice
FAX: 858 677-0940 Web: www.argantix.com Printed in the USA DS KDC 02/05