Hier Klicken für das PDF Dokument!!!

                 CHARGE IT!
                   KEPCO'S ENGINE-START BATTERY CHARGERS




                                                                                                                      KES 12-40 Model (left) and KES 24-50 Model (right)


The KEPCO KES product line is uniquely suitable for any engine-start application.                                             FEATURES
The KES offers the latest in switch mode power supply technology. While most                                                  · Single-Rate Chargers
                                                                                                                              · Analog Current Meter
engine-start chargers do not require an electrically quiet output, the KES boast
                                                                                                                              · Form C Charge-Fault Output
communications quality output, at a switchgear charger price. The KES is also                                                 · Temperature Compensation (Optional)
suitable as a battery eliminator.                                                                                             · Local/Remote ON-OFF


  KES MODEL TABLE
    MODEL               OUTPUT VOLTAGE                  OUTPUT CURRENT LIMIT                                             EFFICIENCY                  OUTPUT PROTECTION (4)
                          (FLOATING)
                    FACTORY     ADJUSTABLE      FACTORY      ADJUSTABLE      SHORT                                 AC INPUT     AC INPUT       OVER        OVER        BATTERY
                    SETTING       RANGE        SETTING (1)     RANGE       CIRCUIT (2)   RIPPLE (3)    NOISE (3)     100V         200V        VOLTAGE     CURRENT     REVERSED(5)
                      V d-c        V d-c          A d-c         A d-c         A d-c       mV rms        mV p-p                                 V d-c        A d-c        A d-c

  12 VOLT MODELS
  KES 12-20          13.4       9.4 - 16.2        20          4 - 20           18          120          150          77%          81%           25           29              29
  KES 12-40          13.4       9.4 - 16.2        40          8 - 40           36          150          200          81%          85%           25           55              58
  24 VOLT MODELS
  KES 24-10          26.8      18.8 - 32.4        10          2 - 10            9          150          200          80%          84%           44           17          14.5
  KES 23-20          26.8      18.8 - 32.4        20          4 - 20           18          200          300          82%          86%           44           29              29
  KES 24-50          26.8      18.8 - 32.4        50          10 - 50          45          200          300          82%          84%           44           70          72.5
  48 VOLT MODELS
  KES 48-5           53.6      37.6 - 55.0         5           1-5             4.5         200          300          81%          85%           60           11          7.25
  KES 48-10          53.6      37.6 - 55.0        10          2 - 10            9          300          400          84%          87%           60           19          14.5
  KES 48-25          53.6      37.6 - 55.0        25          5 - 25           22.5        300          400          84%          88%           60           45          36.3

(1) 4% accuracy for factory set current limit.
(2) 10% of current limit setting value foldback.
(3) Ripple and noise = 1.5 x indicated values for Ta = -10°C to 0°C. Values shown are satisfied for 0 to 100% load, 0 to 65°C. measuring bandwidth   100MHz.
(4) Shutdown upon fault condition. After disconnecting a-c input, remove the fault, wait about 40 seconds, then reconnect a-c input.
(5) Output disconnected for output current > 1.45 x rated current limit. Output limited to a negative Schottky diode drop.

                                       CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
                                       Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11 Avenue, Flushing, NY 11352
                                                            KEPCO INC. · 131-38 Sanford
                                       info@compumess.de · www.compumess.de · www.netzteile.de
Tel: (718) 461-7000 · Fax: (718) 767-1102 · Email: hq@kepcopower.com · www.kepcochargers.com
  KES GENERAL SPECIFICATIONS                                                                                                 KES ENGINE START
  SPECIFICATION              RATING/DESCRIPTION                                CONDITION                                     BATTERY CHARGER
  Temperature                 -10°C to 65°C                     Operating (Output performance
                                                              derated above 50°C and below 0°C)

                             -30°C to +75°C                                    Storage
  Cooling                     Forced air flow                  One fan (exhaust to the left side)
                                                              Two fans (KES 24-50 & KES 48-25)
  Humidity                    10 to 90% RH                      Operating and storage, wet bulb
                                                                     temperature 35°C

  Weight                approx. 9.0 lbs. (4.1 Kg)            KES 12-20, KES 24-10 & KES 48-5
                       approx. 12.0 lbs. (5.4 Kg)           KES 12-40, KES 24-20 & KES 48-10
                        approx. 22.0 lbs. (10 Kg)                    KES 24-50 & KES 48-25
  Dimensions           7.25 x 11.14 x 9 (inches)              All except KES 24-50 & KES 48-25
  HxWxD                184.2 x 283 x 228.6 (mm)                                                                                    KES 12-40 with Optional Temperature Probe
                       9.25 x 15.16 x 9 (inches)                     KES 24-50 & KES 48-25
                       235 x 384.6 x 228.6 (mm)



  KES OUTPUT CHARACTERISTICS
  SPECIFICATION                  RATING/DESCRIPTION                               CONDITION

  Source Effect                     0.2% max.                          85-132V a-c, 170-265V a-c
  Load Effect                     0.6% max. (1)                              0-100% load (2)
  Temperature                        1% max.                                    -10 to 50°C
  Effect
  Time Effect                       0.5% max.                                    1/2 to 8 hr.
  (Drift)                                                                                                                          KES 24-50 with Optional Temperature Probe
  Output Voltage       3mV/(°F)(cell), 5.4mV/(°C)(cell)                 Use optional temperature
  Temperature                 0.5% accuracy                               compensation probe,                     KEPCO INC. has long enjoyed an excellent
  Compensation           @ 2.23V cell voltage (3)                   0°C to +35°C for Lead-Acid battery
                                                                                                                  reputation as a leading manufacturer of
(1) KES 12-20, KES 24-10, KES 48-5: 0.4%.                                                                         precision laboratory and OEM type
(2) Measured at front panel test points; minimum input impedance of 1 Megohm required for voltage
    measurement instrument.
                                                                                                                  power supplies and now brings its 60+
(3) Compensation calculated using: V = ­ (KT) (Ta ­ 77) (VB/2.23) where VB = Battery voltage.                     years of expertise in power conversion to
    KT = 0.003V/ (°F)(cell), Ta = ambient temperature in °F and 2.23 = cell voltage at 77°F.                      the battery charger market.


  KES INPUT CHARACTERISTICS
  SPECIFICATION                    KES 12-20, KES 24-10, KES 48-5     KES 12-40, KES 24-20, KES 48-10      KES 24-50, KES 48-25                        CONDITION

  Voltage Range                                              Nominal: 100-120V a-c, 220-240V a-c
                                                                     Range: 85-265V a-c
  Frequency                                                 Nominal: 50/60Hz; Range: 47-66Hz (1)
  Input Current
    100 to 120V a-c input                4.4A a-c max.                      8.4A a-c max.                    22A a-c max.
    200 to 240V a-c input                2.2A a-c max.                      4.2A a-c max.                    11A a-c max.
  Input Surge
    100 to 120V a-c input                20A p-p max.                       30A p-p max.                     20A p-p max.                          Surge, cold start
                                                                                                                                                  interval > 30 sec.
    200 to 240V a-c input                40A p-p max.                       60A p-p max.                     40A p-p max.
  Leakage Current
         100V a-c input                0.34mA a-c typ.                     0.55mA a-c typ.                 0.65mA a-c typ.                  Per IEC 950 and UL 1950
                                                                                                                                               @ 120V a-c, 60Hz
             240V a-c input            0.46mA a-c typ.                     0.75mA a-c typ.                 1.25mA a-c typ.                  Per IEC 950 and UL 1950
                                                                                                                                               @ 240V a-c, 60Hz
  Power Factor                                                                 0.99 typ.                                                   100V a-c input, rated output

(1) KES units can operate with source power frequency up to 400Hz nominal (range to 440Hz). Power factor, efficiency and leakage current will derate as frequency increases.
    Consult factory for additional information.


                     For more info, visit our Website: www.kepcochargers.com
                            CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
                                      Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
                                      info@compumess.de · www.compumess.de · www.netzteile.de