California Instruments MX Series II 15135 kVA
Overview 150400 V
· High Power AC and DC Power Source
Programmable AC and DC power for frequency 0375 A / Phase
conversion and product test applications
· Expandable Power Levels 208 230 400
Available output power of 15, 30, and 45 kVA
per unit and multi-unit configurations for power
requirements up to 135 kVA and above
480
· Single and Three Phase Mode
Phase mode programming on MX30-3Pi and
MX45-3Pi allows switching between single and
three phase output modes
· Arbitrary & Harmonic Waveform
Generation
User defined voltage waveform and
distortion programming USB and LAN remote control interfaces and
instrument drivers for popular ATE programming
· Regenerative, bidirectional "Green"
environments are available. This allows the MX
Power Solution
Series to be easily integrated into an automated
Automatic crossover between Source and Sink
test system.
power mode offers regenerative capabilities in AC,
AC+DC and DC modes. Regenerate up to 100% For advanced test applications, the programmable
of the rated output power back to the utility grid controller version offers full arbitrary waveform
during sink mode operation. ( -SNK option ) generation, time and frequency domain
measurements, and voltage and current
· Remote Control
waveform capture.
Standard RS232C & USB along with optional IEEE-
488 & LAN Interfaces are available for automated Configurations
test applications The MX15 delivers up to 15 kVA of single phase
output. The MX30 delivers up to 30 kVA, and the
Introduction MX45 up to 45 kVA. Both operate using single
The MX Series consists of multiple high power AC or three phase output in AC mode. In DC mode,
and DC power systems that provide controlled 50% of the AC power level is available. On MX-P
AC and DC output for ATE and product test models, AC+DC mode is also supported.
applications.
For higher power requirements, the MX90 and
This high power AC and DC test system covers a MX135 models are available. Multi cabinet
wide spectrum of AC and DC power applications MX45 systems always operate in three phase
at an affordable cost. Using state-of-the-art PWM output mode. Available reconfigurable MX90
switching techniques, the MX series combines and MX135 models (-MB designation) provide
compactness, robustness and functionality in a multiple controllers which allow separation of the
compact floor-standing chassis, no larger than high power system into two or three individual
a typical office copying machine. This higher MX45 units for use in separate applications. This
power density has been accomplished without ability to reconfigure the system provides an even
the need to resort to elaborate cooling schemes greater level of flexibility not commonly found in
or additional installation wiring. Simply roll the power systems.
MX15, MX30, or MX45 unit to its designated
Product Evaluation and Test
location (using included casters), plug it in, and
Increasingly, manufacturers of high power
the MX series is ready to work for you.
equipment and appliances are required to fully
Simple Operation evaluate and test their products over a wide
The MX Series can be operated completely from range of input line conditions. The built-in output
its menu driven front panel controller. A backlit transient generation and read-back measurement
LCD display shows menus, setup data, and capability of the MX Series offers the convenience
read-back measurements. IEEE-488, RS232C, of a powerful, and easy to use, integrated test
system.
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
858.458.0223 sales@ProgrammablePower.com
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11 · www.compumess.de · www.netzteile.de 217
MX Series II
Regenerative, bidirectional "Green" ranges are required, the programmable range
Power Solution change option (-R) provides the ability to switch
The MX Series features the ability to both source between both output ranges. Pi version models
and sink current, i.e. bi-directional current offer standard dual voltage ranges.
flow. The MX amplifier is designed to reverse
For applications requiring more than 300 V
the phase relationship between the AC input
L-N (or 520 V L-L), the optional -HV output
voltage and current in order to feed power back
transformer provides an additional 400 V L-N
onto the utility grid. This mode of operation is
and 693 V L-L output range for use in AC mode
particularly useful when testing grid-tied products
only.
that feed energy back onto the grid. Static
Power Converters such as grid-tied and off-grid Multi-Box Configurations
photovoltaic inverters are tested for frequency For high power applications, two or three
variations, voltage transients, DC injection and MX45 chassis can be combined to provide 90
harmonic susceptibility. to 135 kVA of three phase power. MX90 and
MX135 systems are always configured for three
phase operation. Contact sales for custom
configurations.
High Crest Factor
With a crest factor of up to 3.6, the MX Series
Programming sink (-SNK) mode operation
AC source can drive difficult nonlinear loads with
Avionics ease. Since many modern products use switching
With an output frequency range to 819 Hz power supplies, they have a tendency to pull
(or 1000 Hz with -HF option), the MX Series is high repetitive peak currents. The MX30-3Pi can
well suited for aerospace applications. Precise deliverup to 240 Amps of repetitive peak current
frequency control and accurate load regulation (150 V AC range) per phase to handle three
are key requirements in these applications. The phase loads.
available IEEE-488 remote control interface
Remote Control
and SCPI command language provide for easy
Standard RS232C & USB IEEE-488 along with
integration into existing ATE systems. The MX
optional LAN remote control interfaces allow
Series eliminates the need for several additional
programming of all instrument functions from an
pieces of test equipment, saving cost and space.
external computer. The popular SCPI command
Instrument drivers for popular programming
protocol is used for programming.
environments such as National Instruments
LabViewTM are available to speed up system Application Software
integration. Windows® application software is included.
This software provides easy access to the power
Regulatory Testing
source's capabilities without the need to develop
As governments are moving to enforce product
any custom code. The following functions are
quality standards, regulatory compliance testing
available through this GUI program:
is becoming a requirement for a growing number
of manufacturers. The MX Series is designed · Steady state output control (all parameters)
to meet AC source requirements for use in · Create, run, save, reload and print
compliance testing such as IEC 61000, 3-2, 3-3, transient programs
3-11, 3-12, to name a few. · Generate and save harmonic waveforms.
· Generate and save arbitrary waveforms.
Choice of voltage ranges
· Measure and log standard measurements
The MX30 and MX45 can be ordered with either
· Capture and display output voltage and
a 150 V RMS Line to Neutral output voltage
current waveforms.
range or a 300 V RMS Line to Neutral range. This
· Measure, display, print and log harmonic
provides 3 phase output capability of 260 Vac or
voltage and current measurements.
520 Vac line to line respectively. If dual output
· Display IEEE-488, RS232C, USB and LAN bus
traffic to and from the AC Source to help you
develop your own test programs.
1. Requires PC running WindowsXPTM or Windows 2000TM.
218 www.ProgrammablePower.com
MX Series II 15135 kVA
Harmonically distorted waveform.
MX Series - AC and DC Transient Generation
The MX Series controller has a powerful AC
and DC transient generation system that allows
complex sequences of voltage, frequency and
waveshapes to be generated. This further
enhances the MX's capability to simulate AC line
conditions or DC disturbances. When combined
Harmonic Waveform Generation with the multiphase arbitrary waveform
Using the latest DSP technology, the MX capabilities, the AC and DC output possibilities
Series programmable controller is capable of are truly exceptional. Transient generation is
generating harmonic waveforms to test for controlled independently yet time synchronized
harmonics susceptibility. The Windows Graphical on all three phases. Accurate phase angle control
User Interface program can be used to define and synchronized transient list execution provide
harmonic waveforms by specifying amplitude and unparalleled accuracy in positioning AC output
phase for up to 50 harmonics. The waveform events.
data points are generated and downloaded by
the GUI to the AC source through the IEEE-488 or Transient programming is easily accomplished
RS232C bus. Up to 200 waveforms can be stored from the front panel where clearly laid out menu's
in nonvolatile memory and given a user defined guide the user through the transient definition
name for easy recall. process.
All MX-Pi Series configurations offer three phase The front panel provides a convenient listing
waveform generation, allowing independent of the programmed transient sequence and
phase anomalies to be programmed. It also allows for transient execution Start, Stop,
allows simulation of unbalanced harmonic line Abort and Resume operations. User defined
conditions. transient sequences can be saved to non-volatile
memory for instant recall and execution at a
Arbitrary Waveform Generation later time. The included Graphical User Interface
Using the provided GUI program or custom program supports transient definitions using
software, the user also has the ability to define a spreadsheet-like data entry grid. A library
arbitrary AC waveforms. The arbitrary waveform of frequently used transient programs can be
method of data entry provides an alternative created on disk using this GUI program.
method of specifying AC anomalies by providing
specific waveform data points. The GUI program
provides a catalog of custom waveforms and also
allows real-world waveforms captured on a digital
oscilloscope to be downloaded to one of the
many AC source's waveform memories. Arbitrary
Transient List Data Entry from the front panel.
waveform capability is a flexible way of simulating
the effect of real-world AC power line conditions
on a unit under test in both engineering and
production environments.
Harmonic waveform, Fund., 3rd, 5th, 7th, 9th,11th and 13th.
Two hundred user defined waveforms. Transient List Data Entry in GUI program.
858.458.0223 sales@ProgrammablePower.com 219
MX Series II
MX Series - Measurement and Analysis Waveform Acquisition
The MX Series is much more than a The measurement system is based on real-time
programmable AC, DC or AC+DC power source. digitization of the voltage and current waveforms
It also incorporates an advanced digital signal using a 4K deep sample buffer. This time domain
processor based data acquisition system that information provides detailed information on
continuously monitors all AC source and load both voltage and current waveshapes. Waveform
parameters. This data acquisition system forms acquisitions can be triggered at a specific phase
the basis for all measurement and analysis angle or from a transient program to allow
functions. These functions are accessible from the precise positioning of the captured waveform
front panel and the remote control interface for with respect to the AC source output.
the MX Series (MX15 excluded; uses 2-line display
The front panel LCD displays captured waveforms
shown below).
with cursor readouts (excluding MX15). The
Conventional Measurements [All controllers] included GUI program also allows acquired
Common AC and DC measurement parameters waveform data to be displayed, printed, and
are automatically provided by the data acquisition saved to disk.
system. These values are displayed in numeric
form on the front panel LCD display. The
following measurements are available: Frequency,
Vrms, Irms, Ipk, Crest Factor, Real Power (Watts),
Apparent Power (VA) and Power Factor.
Harmonic Analysis
The MX Series provides detailed amplitude and Acquired Current waveform (MX30/45 Display).
phase information on up to 50 harmonics of
the fundamental voltage and current (up to 16
kHz in three phase mode) for either one or three
phases. Harmonic content can be displayed
in both tabular and graphical formats on the
front panel LCD for immediate feedback to the Acquired Voltage waveform (MX30/45 Display).
operator (excluding MX15). Alternatively, the
included GUI program can be used to display,
print and save harmonic measurement data. Total
harmonic distortion of both voltage and current is
calculated from the harmonic data.
Measurement data for single phase (MX30/45 Display).
Absolute amplitude bar graph display of current harmonics Measurement data for all three phases (MX30/45 Display).
with cursor positioned at the fundamental (MX30/45 Display).
Voltage harmonic measurement table display in absolute
values (MX30/45 Display)
Acquired three phase voltage waveforms display on PC.
220 www.ProgrammablePower.com
MX Series II : Specifications 15135 kVA
Operating Modes
Pi Version AC, DC and AC+DC
AC Mode Output
Frequency Range: 16.00-819.0 Hz, -LF Option: 16.00-500.0 Hz, -HF Option: 16.00-1000 Hz (supplemental specifications apply above
819 Hz). Resolution: 0.01 Hz: 16.00 - 81.91 Hz, 0.1 Hz: 82.0 Hz - 819.1 Hz, 1 Hz: 820-1000 Hz
Phase Outputs MX15-1/15-1Pi: 1, MX30/45-3Pi: 1 or 3 switchable, Neutral: Floating, Coupling: DC (except for -HV option)
Total Power MX15-1/1Pi: 15 kVA, MX30-1/3: 30 kVA, MX45-1/3: 45 kVA, MX90: 90 kVA, MX135: 135 kVA
Load Power Factor 0 to unity at full output current
AC Mode Voltage
Voltage Ranges Range V Low V High Load Regulation < 0.25 % FS DC to 100 Hz, < 0.5 % FS 100 Hz to 819 Hz
AC 0-150 V 0-300 V Line Regulation < 0.1% FS for 10 % line change
AC+DC 0-150 V 0-300 V
External Sense Voltage drop compensation (5% Full Scale)
Harmonic Distortion (Linear) Less than 0.5% from 16 - 66 Hz, Less than 1% from 66 - 500 Hz, Less than 1.25% above 500 Hz
DC Offset < 20 mV
Load Regulation 0.25% FS @ DC - 100 Hz, 0.5% FS > 100 Hz
External Amplitude Modulation Depth: 0 - 10 %, Frequency: DC - 2 KHz
Voltage slew rate 200 µs for 10% to 90% of full scale change into resistive load, 0.5V / µSec
AC Mode Current
Steady State AC Current @ FS V Model MX15-1Pi MX30-3Pi / 1Pi MX45-3Pi / 1Pi MX90-3/Pi MX135-3/Pi
V Low 100 66.6/ø / 200 100/ø / 300 200/ø 300/ø
V High 50 33.3/ø / 100 50/ø / 150 100/ø 150/ø
Note: Constant power mode provides increased current at reduced voltage. See chart below
Peak Repetitive AC Current Up to 3.6 x rms current at full scale voltage
Programming Accuracy Voltage (rms): ± 0.3 Vrms, Frequency: ± 0.01 % of programmed value, Current Limit: - 0 % to + 5 % of programmed value + 1A, Phase:
< 0.5° + 0.2°/ 100 Hz with balanced load
Programming Resolution Voltage (rms): 100 mV, Frequency: 0.01 Hz from 16 - 81.91 Hz, 0.1 Hz from 82.0 - 819 Hz, Current Limit: 0.1 A, 3 phase mode,
1.0 A, 1 phase mode, Phase: 0.1°
Constant Power AC Mode - Available Max. AC Current
125%
Current
(RMS) 100%
Full
50% Power
20%
10% 50% 80% 100%
Voltage (RMS)
Note: Specifications are subject to change without notice. Specifications are warranted over an ambient temperature range of 25°± 5° C. Unless otherwise noted, specifications are per phase
for a sinewave with a resistive load and apply after a 30 minute warm-up period. For three phase configurations, all specifications are for L-N. Phase angle specifications are valid under
balanced load conditions only.
© 2009 AMETEK Programmable Power All rights reserved. AMETEK Programmable Power is the trademark of AMETEK Inc., registered in the U.S. and other countries. Elgar, Sorensen,
California Instruments, and Power Ten are trademarks of AMETEK Inc., registered in the U.S.
858.458.0223 sales@ProgrammablePower.com 221
MX Series II : Specifications
Measurement
Measurements - Standard Parameter Frequency RMS RMS Peak Crest Real Apparent Power Phase DC DC Power
(AC Measurements) Voltage Current Current Factor Power Power Factor Voltage Current
Range 16-100 Hz 0-400 V 0-160 A 0-400 A 0.00-6.00 0-15 kW 0-15 kVA 0.00-1.00 0.0-360.0 0-400 V 0-160 A Power
100-820 Hz
Accuracy* 0.01% + 0.05 V + 0.15 A + 0.15 A + 0.05 30 W + 30 VA + 0.01 2.0° 0.5 V 0.5 A 0.15 kW
(±) 0.01 Hz 0.02% .02% 0.02% 0.1% 0.1%
0.1 V + 0.3 A + 0.3 A + 0.05 60 W + 60 VA + 0.02 3.0°
0.02% 0.02% 0.02% 0.1% 0.1%
Resolution* 0.01 Hz / 10 mV 10 mA 10 mA 0.01 10 W 10 VA 0.01 0.1° 10 mV 10 mA 10 W
0.1 Hz
* Measurement system bandwidth = DC to 6.7 kHz. Accuracy specifications are valid above 100 counts. Current and Power Accuracy and Range specifications are
times three for MX90, MX135 or MX30/45-3Pi in single phase mode. PF accuracy applies for PF > 0.5 and VA > 50 % of range
Measurements - Harmonics Parameter Frequency Fundamental Harmonics Phase Voltage Current
(Pi controller only) Range 16.00-1000.0 Hz / 32.00 Hz - 16 kHz 0.0 - 360.0° Fundamental Harmonics 2-50 Fundamental Harmonics 2-50
Accuracy* (±) 0.03% + 0.03 Hz / 0.01 Hz 2° typ. 750 mV 0.3% + 750 mV+0.3% /1 kHz 0.5 A / 0.3% + 150 mA +0.3% /1 kHz
Resolution 0.01 Hz 0.5° 10 mV / 10 mV 100 mA / 100 mA
* Accuracy specifications are valid above 100 counts. Accuracy specifications are for three phase mode. Harmonics frequency range for MX30/45-3Pi in single phase
mode is 32 Hz - 48 kHz
DC Mode Output
Power Maximum DC power at full scale of DC voltage range. MX15-1Pi: (10 kW), MX30-3Pi: (6.5 kW per output, 3 outputs. 20 kW in
1 channel mode), MX45-3Pi: (10 kW per output, 3 outputs. 30 kW in 1 channel mode)
Voltage Ranges Range: Low (0 - 200 V), High (0 - 400 V)
Output Accuracy ± 1 Vdc
Load Regulation < 0.25 % FS
Line Regulation < 0.1% FS or 10 % line change
Ripple < 2 Vrms Lo Range, < 3 Vrms Hi Range
Max DC Current @ FSV per output Model MX15-1Pi MX30-3Pi / 1Phs MX45-3Pi / 1Phs MX90-3/Pi MX135-3/Pi
V Low 50 33.3 / 100 50 / 150 100 150
V High 25 16.6 / 50 25 / 75 50 75
Note: Constant power mode provides increased current at reduced voltage. See chart on previous page
Current Limit Programmable from 0 A to max. current for selected range
AC+DC Mode Output
Output (Pi) Power Maximum current and power in AC+DC mode is same as DC mode
Protection
Over Load Constant Current or Constant Voltage mode
Over Temperature Automatic shutdown
Storage
Non Volatile Mem. storage 16 instrument setups, 200 user defined waveforms [Pi only]
Waveforms
Waveform Types Std: Sine, Pi: Sine, Square, Clipped sine, User defined
User defined waveform storage Four groups of 50 user defined arbitrary waveforms of 1024 points for a total of 200. One group can be active at a time
System Interface
Inputs Remote shutdown, External Sync, Clock/Lock
Outputs Function Strobe / Trigger out, Clock/Lock
Remote Control (Pi standard with -P option)
IEEE-488 Interface IEEE-488 (GPIB) talker listener. Subset: AH1, C0, DC1, DT1, L3, PP0, RL2, SH1, SR1, T6, IEEE-488.2 SCPI Syntax
RS232C Interface 9 pin D-shell connector (Supplied with RS232C cable)
LAN ( option ) Ethernet Interface: 10BaseT, 100BaseT, RJ45
USB Version: USB 1.1; Speed: 460 Kb/s maximum
Output Relay Push button controlled or bus controlled output relay
Output impedance Programmable Z available on MX30-3Pi and MX45-3Pi in 3 phase mode only. Specifications apply at 50 Hz fundamental.
( not available with -SNK Option ) Resistive: 1 - 200 mOhm, Inductive: 15 - 200 uH
222 www.ProgrammablePower.com
MX Series II : Specifications 15135 kVA
AC Input
Voltage Must be specified at time of order. All inputs are L-L, 3ø, 3 wire + Gnd. 208 ± 10% VAC, 230 ± 10% VAC, 400 ± 10% VAC,
480 ± 10% VAC
Input Line Current (per phase) Current (MX15): Current (MX30/45):
V L-L 208 230 400 480 V L-L 208 230 400 480
St State 58.3 ARMS 52.3 ARMS 30 ARMS 25 ARMS St State 116/175 ARMS 105/157 ARMS 60/90 ARMS 50/75 ARMS
Distortion: < 8 % at full power < 20 % below 35 % of power
Line Frequency 47 - 63 Hz
Efficiency 85 % typical
Power Factor 0.95 typical
AC Service
Inputs/Outputs MX30/MX45: Front access, cables routed through rear panel, exit in back. MX15: Rear Access
Regulatory IEC61010, EN50081-2, EN50082-2, CE EMC and Safety Mark requirements
EMI CISPR 11, Group1 , Class A
Connectors AC Input & Output terminal block behind front cover, IEEE-488 (GPIB) connector (rear panel), 9 pin D-Shell RS232C connector*, (rear
panel), Remote voltage sense terminal block (rear panel), System Interface Connector, DB-37 (rear panel). *RS232 DB9 to DB9 cable
supplied
Physical Dimensions
MX30/MX45 Dimensions Height: 50.0" (1270 mm), Width: 28.75" (731 mm), Depth: 34.5" (876 mm)
MX30/MX45 Weight Chassis: Net: 1150 lbs / 522 Kg, Shipping: 1231 lbs / 560 Kg, Amp Module: Net: 63 lbs / 29 Kg
MX15 Dimensions Height: 31.75" (806 mm), Width: 24.0" (610 mm), Depth: 28.0" (711 mm)
MX15 Weight Chassis: Net: 600 lbs / 272 Kg, Shipping: 681 lbs / 309 Kg, Amp Module: Net: 63 lbs / 29 Kg
Chassis MX30/MX45: Casters and forklift openings. MX15: Casters
Vibration and Shock Designed to meet NSTA project 1A transportation levels. Units are shipped in wooden crate with forklift slots
Air Intake/Exhaust Forced air cooling, front air intake, rear exhaust
Operating Humidity 0 to 95 % RAH, non condensing
Temperature Operating: 0 to 40° C (30° C max in CP mode), Storage: -20 to +85° C
Programmable controller versions with dual voltage ranges
Model AC Output Power Phase Outputs AC/DC Voltage Range Controller
MX15-1Pi 15kVA 1 150/200 & 300/400 Programmable
MX30-3Pi 30 kVA 1&3 150/200 & 300/400 Programmable
MX45-3Pi 45 kVA 1&3 150/200 & 300/400 Programmable
MX90-3Pi 90 kVA 3 150/200 & 300/400 Programmable
MX135-3Pi 135 kVA 3 150/200 & 300/400 Programmable
Pi models include IEEE-488, RS232C & USB interfaces, Advanced measurements, arbitrary waveform generation. Phase mode switching on MX-30/45-3Pi.
-MB Option
Model AC Output Power Phase Outputs AC/DC Voltage Range Controller
MX90-3Pi-MB 90 kVA 3 150/200 & 300/400 Dual MX45-3Pi
MX135-3Pi-MB 135 kVA 3 150/200 & 300/400 Triple MX-45-3Pi
Reconfigurable systems can be separated into stand-alone MX45-3Pi models or combined for higher power levels.
Steady State AC RMS Current in Regeneration Mode ( -SNK Option )
Model MX15-1Pi MX30-3Pi MX45-3Pi MX60-3Pi MX90-3Pi MX135-3Pi
V Low 100A 66.6/Ø / 200 100A/Ø/300 133.3/Ø 200/Ø 300/Ø
V High 50A 33.3/Ø / 100 50A/Ø/150 66.6/Ø 100/Ø 150/Ø
858.458.0223 sales@ProgrammablePower.com 223
MX Series
Model -413 *IEC 1000-4-13 Harmonics &
Refer to table shown for model numbers and Interharmonics test firmware.
configurations.
-704 Mil Std 704 A - F test - firmware/ software.
Supplied with
-ABD ABD0100.1.8 Test Option.
Standard: User Manual on CD ROM.
Pi version: User/Programming Manual and Software -AMD Airbus AMD24 Test
on CD ROM. RS232C serial cable. -A350 Airbus Test Software
Input Voltage Settings -B787 Boeing 787 Test Software
Specify input voltage (L-L) setting for each MX
system at time of order: -HV Adds 400 V L-N AC-only output range.
208 Configured for 208 V ±10 % L-L, -LF Limits max. frequency to 500 Hz.
4 wire input.
230 Configured for 230 V ±10 % L-L, -HF Increases max. frequency to 1000 Hz.
4 wire input. -XV Adds other AC-only output range.
400 Configured for 400 V ±10 % L-L, Consult factory.
4 wire input.
480 Configured for 480 V ±10 % L-L, -LKM Clock/Lock Master
4 wire input -LKS Clock/Lock Auxiliary
Standard Model Options -WHM Watt-Hour Measurement option.
Specify output range on standard models. All
range values shown are Line to Neutral. -SNK Bidirectional auto source and sink mode.
Offers up to 100% power sink capability.
- 150 Configured for 150 V AC and
200 V DC output ranges. Packaging and Shipment
- 300 Configured for 300 V AC and All MX systems are packaged in re-usable protective
400 V DC output ranges. wooden crates for shipment.
Pi Model Options Feature Comparison
-160 RTCA/DO-160D, DO-160E, and Model Pi
EUROCAE test firmware. AC mode X
DC mode X
-411 *IEC 1000-4-11 test firmware.
AC+DC mode X
- LF Limits maximum frequency to 500 Hz. Dual V Range X
-P IEEE-488 & RS232C Interface Adds Transient programming X
programming, Windows & RS232 Cable. Arbitrary waveforms X
Measurements X
-LAN Ethernet Interface. Harmonic measurements X
- HF Increases max frequency to 1000 Hz. Waveform acquisition X
1 or 3 Phase mode MX30/45-3Pi
-R Range change. Provides 150/200 & 300/ IEEE / RS232 X
400 AC/DC output ranges. (Std. MX15)
MX15 Dimensions - single chassis MX30/MX45 Dimensions - single chassis
31.75 28.75
[806.45] [730.25]
48.125
[1222.4]
00
28. .20]
[ 711 0
24.0 0]
.8
[609
1.95
Rear View Front View [49.53]
Rear View Front View