Hier Klicken für das PDF Dokument!!!

Sorensen SFA Series                                                                                                                                       5­150 kW
High Slew Rate Current Source                                                                                                                              60­160 V
The SFA family builds on the industry leading
Sorensen SGA series to provide a high power
                                                                                                                                                        31­2500 A
current source for laser diode applications. State
of the art high power laser diodes require well-
regulated current control to avoid catastrophic                                                                                                      208         400           480
damage. Under anomalous operating conditions,
excessive stored energy in the output circuit of
the power supply can result in peak stresses that
can permanently damage the device. Providing a
constant current regulation mode only, the SFA's
low stored energy output minimizes damage
potential for sensitive devices as well as enabling
a current slew rate of up to 400 A/msec.
                                                                          3U                                                                 6U
                 Power                            5 kW                  10 kW                  15 kW                   20 kW                 25 kW                30 kW
                 Voltage                                                               Maximum Current (parallel for higher current. )
                   60                               83                   167                 250                       333                    417                   500
                  100                               50                   100                 150                       200                    250                   300
                  160                               31                   63                   94                       125                    156                   188
 Specifications (at nominal AC line and 25ºC)
 Output Slew Rate (10-90% resistive load)   250A/ms (400A/ms typical) rise, 200A/ms typical fall; 160V model 87A/ms/5kW (145A/ms/5kW typical), 60A/ms, typical, fall
 Control Mode                               Current Control Only
 Front Panel Meter Accuracy                 Voltage ±0.5% of full-scale + 1 digit, Current ±0.5% of full-scale + 1 digit
 Load Regulation                            (no load to full load, nominal AC input) Current 0.1% of rated output current
 Line Regulation                            (±10% of nominal AC input) Current 0.05% of rated output current
 Current Ripple                             1% p-p of full-scale current
 Transient Response                         Output current recovers to within 1% of current setpoint within 1ms for a 10 to 100% or 100% to 10% step load change
 Current Overshoot                          Maximum 8% of full-scale for 0 to 100% change into a resistive load
 Output Capacitance                         60V Models <10 µF / 5 kW, 100/160V Models 3 µF / 5 kW
 Stability                                  ±0.05% of setpoint after 8­hr. warm-up at fixed line, load, and temperature using remote sense
 Power Factor                               >0.9 typical for 208/220VAC input, >0.78 typical for 380/400VAC input, >0.7 typical for 440/480VAC input
 Remote Analog Control                      Current Setpoint Accuracy, ±0.8% of full-scale output; Overcurrent Protection, ±1% of full-scale output;
                                            Resistive Control, 0­5k = 0-100% Current; Voltage Control, 0­5 or 0­10 VDC = 0-100% Current;
                                            Overcurrent Protection, 0­5.5 VDC = 0-110%
 Efficiency                                 87% typical at full load, nominal line
 Remote Control/Monitor                     On/Off control via contact closure, 6-120 VDC or 12-240VAC, and TTL or CMOS switch, current monitor, OCP limit set,
                                            summary fault status
 Overvoltage Protection                     Fixed at approximately 110% of the rating compliance voltage. Reset requires cycling the front panel standby power switch off/on
 Ethernet Control (optional)                LXI compliant 10/100 Base T Ethernet remote control with web server for direct control of power supply via web browser.
 Isolated Analog Control (optional)         Input to Output Isolation: 500 V Compliant with maximum terminal float voltage.
                                            Recommended operation under SELV normal conditions.
 Regulatory                                 Certified to UL/CSA 61010 and IEC/EN 61010-1, CE Compliant (LVD and EMC Directives), Input power options
 Input Power Configuration                  3­phase, 3­wire plus ground. Not phase, rotation sensitive. Neutral not used.
 Input Power Voltage Selection              208/220 VAC±10%, 47 to 63 Hz, 380/400 VAC±10%, 47 to 63 Hz, 440/480 VAC±10%, 47 to 63 Hz
 Environmental
 Ambient Operating Temperature              0 to 50°C
 Storage Temperature                        -25 to 65°C
 Temperature Coefficient                    Current Setpoint 0.03%/°C of rated current
 Cooling                                    Internal Fans. Zero clearance stacking
 Humidity                                   0 to 90% at 40°C; 0 to 50% at 25°C, non-condensing
 Altitude                                   Full power at 5,000 feet, 10% derating of full power for every 1,000 feet above 5,000 feet
 Physical
 5 to 15 kW in 3U                           19.00in W x 25.12in D x 5.25inH; 80 lbs., (48.3cm W x 63.8cm D x 13.3cm H; 36 kg)
 20 - 30 kW in 6U                           19.00in W x 25.12in Dx 10.5in x H; 160 lbs., (48.3cm W x 63.8cm D x 36.7cm H; 73 kg)
 Accessories
 K550212-01                                 3U Rack Slides (for 5kW, 10kW and 15kW models)
 K550213-01                                 6U Rack Slides (for 20kW, 25kW and 30kW models)

                           CompuMess Elektronik GmbH · sales@ProgrammablePower.com
                       858.458.0223                                     Lise-Meitner-Str. 1 · D-85716 Unterschleißheim                                                               73