Hier Klicken für das PDF Dokument!!!

Quiet Linears                                                          Linear Technology
! Low Noise, Low Distortion
  Clean AC power output for noise
                                                                       AC Power Source
  sensitive applications                                                   TL Series
! 350 VA or 250 VA Output Power
  Capable of handling many special
  purpose AC power applications
! 16 Hz to 8000 Hz Frequency Range
  Commercial, Military and Avionics
  applications
! Precision Measurements
  Accurately measures TRMS Volt,
  TRMS Current, Peak Current, Crest
  Factor, Real Power and Power Factor
  when equiped with measurement
                                                                                      Model 351TL
  option.
! Remote Control
  Available IEEE-488 and RS232C
  Interface for automated test applica-
  tions. Includes WindowsTM operating
  software

Compact AC Power                         Easy To Use Controls                        Special Applications
   Using state of the art linear tech-      Front panel digital rotary encod-          Applications requiring high fre-
nology, the TL Series program-           ers are used to set voltage and fre-        quency output such as gyro's, sen-
mable AC power sources are ide-          quency and current limit. These con-        sors and variable frequency control-
ally suited for applications where a-    trols have an analog feel, with the         lers can be tested and operated by
low distortion, low noise sinewave       precision and reliability of digital cir-   a TL Series unit at up to 8000 Hz.
is required.                             cuits. Settings and measurements            Contact factory for higher frequency
   Selectable input voltage ranges       are read directly on the large, high        requirements.
allow this power source to be used       contrast LCD displays.
anywhere in the world to provide a          Dual output voltage ranges of 135        Output Power
convenient source of variable volt-      Vrms L-N and 270 Vrms L-N, pro-                The 351TL AC power source is
age and frequency power for test-        vide maximum current at the re-             rated for 350 VA with an output volt-
ing and evaluating AC powered            quired voltage.                             age between 90 % and 100 % of
equipment. All common line voltage          The output frequency can be var-         range and a load power factor of 0.7
and frequency combinations are           ied from 16 Hz up to 8000 Hz to             to reflect typical operating condi-
covered.                                 cover commercial, avionics and              tions. Maximum RMS current is 2.8
   In addition, the frequency range      defense power applications.                 A in the 135 V range. The 251TL is
extends to 8000 Hz, making these                                                     rated for 250 VA with an output volt-
products suitable for both conven-       Product Development                         age between 78 % and 100 % of
tional and special purpose applica-         The precise voltage regulation,          range and a load power factor of 0.7.
tions.                                   low distortion and noise levels and         It's maximum current is 2.4 A in the
   Accurate measurement functions        wide frequency range of the TL Se-          135 V range.
are available as an option to elimi-     ries, combined with its easy to use
nate the need for external test          front panel, make it a great preci-
equipment in many test setups. Volt-     sion Lab AC source. Built in mea-
age, current, peak current, power,       surements may be added (option -
and power factor can be read di-         OP1) to extend the units usefulness
rectly on the large LCD display or       for design applications of AC pow-
over the bus.                            ered products.
TL Series - For Easy Transient Programming
                                                Extensive Transient Control1
                                                  With the addition of the remote control interface option, TL Series units
                                                are capable of producing transients with a high degree of user program-
                                                mability. Setting up transient programs is facilitated by a WindowsTM
                                                Graphical User Interface program that allows amplitude, frequency and
                                                event duration to be programmed from a PC. Time resolution is 1 ms
                                                (0.001 sec) with a minimum time interval ranging from 1 to 40 ms, de-
                                                pending on the transient type. Maximum transient time intervals are 9999
                                                seconds. Transient programming allows the effects of common line dis-
                                                turbances such as voltage surges, sags, drop-outs and frequency fluc-
                                                tuations on the unit under test to be evaluated.
Drop transient causes output voltage to drop
to zero for a user specified period
                                                Precision Measurements
                                                  For bench or automated test equipment (ATE) applications, the TL
                                                Series can be ordered with the -OP1 option, offering both IEEE-488 and
                                                RS232C remote control interfaces as well as extended measurements.
                                                These measurements are available from the front panel and over the
                                                bus. The TL Series uses closed-case calibration for both output and
                                                measurement calibration, lowering cost of ownership.

                                                SCPI Protocol Programming Commands
                                                  All functions of the TL Series are programmable over the available
                                                IEEE-488 or RS232C interface. For example, the following tasks can be
                                                performed over the bus:
                                                 · Set voltage to any level
Voltage Surge transient causes output
                                                 · Change frequency
voltage to surge.                                · Generate voltage dropouts, sags or surges
                                                 · Measure TRMS current, peak current, crest factor, TRMS voltage,
                                                    true power, apparent power and power factor
                                                 · Recall eight complete instrument setups from non-volatile memory
                                                 · Adjust current limit value
                                                 · Lock the front panel to prevent operator interference
                                                 · Switch between high and low voltage range
                                                 · Drop output voltage at specific phase angles for specified durations

                                                Application Software
                                                   WindowsTM application software is included with the -OP1 option pack-
                                                age. This easy to use graphical interface program provides complete
                                                control over all in-
Frequency Sweep transient causes the output     strument func-
frequency to change at a user specified rate.   tions using the
                                                RS232C or IEEE-
                                                488 interface.
                                                With enhanced
                                                capabilities such
                                                as output se-
                                                quencing, data
                                                logging and tran-
                                                sient generation,
                                                many applica-
                                                tions can be ad-
                                                dressed without
                                                the need to write
                                                software.            Free WindowsTM Graphical User Interface software included with
Voltage Sweep transient causes output                                option package OP1.
voltage to change at a programmed rate.



Note 1: Voltage drop out transients can be programmed at random phase angles or at 0, 90, 180 and 270 degrees.
                                                                                                    Specifications
                                           Parameter                                              251TL           351TL        Unit
   California                              Controller
   Instruments                                      Type
                                                    Controls
                                                                                                            Programmable
                                                                                                          Digital Encoders
     Total Customer Satisfaction is                 Readouts                                            dual 4 digit LCD's
                                                    Non Volatile Setups (with -OP1 option)                             1 (8)
   the goal of all California Instru-
                                           Output
   ments' employees. It is the driv-                AC Power             maximum                       250              350    VA
                                                    Load Connection                            Rear panel terminal block
   ing force behind everything we do.                                                                      Floating neutral
   This not only affects the product                Voltage
                                                    High range / Low range                                0 - 270 / 0 - 135    V RMS
   that you purchase from California
                                                    Accuracy             16 Hz - 100 Hz                                ± 0.1   % FS
   Instruments, but everything about                                     100 Hz - 5000 Hz                              ± 0.2   % FS
                                                                         5000 Hz - 8000 Hz                             ± 0.3   % FS
   your interface with the company.                 Resolution                                                           0.1   V
   Our applications engineers are                   Load Regulation       < 2000 Hz                                      0.1   % FS
                                                                          2000-5000 Hz                                  0.15   % FS
   ready to assist you with your AC                                       > 5000 Hz                                     0.25   % FS
                                                    Line Regulation      10 % Line change                            ± 0.02    % FS
   power application. With over 35                  T.H.D. (into a       16 Hz - 999 Hz                                < 0.5   %
   years of experience designing and                  resistive load)    1000 Hz - 8000 Hz                             < 2.0   %
                                                    Output Noise         full scale at full power                   .-73 dB    Max.
   building precision AC power sup-                 Frequency (See V-F Rating chart)
                                                    Range                                                        16 - 8000     Hz
   plies, chances are we can meet
                                                    Accuracy                                                         ± 0.02    %
   your needs and exceed your ex-                   Resolution           16.00 Hz - 79.99 Hz                           0.01    Hz
                                                                         80.0 Hz - 799.9 Hz                              0.1   Hz
   pectations. The same dedication                                       800 Hz - 8000 Hz                                  1   Hz
   to customer satisfaction you will                Current (Maximum, see Power Ratings side bar)
                                                    RMS Current          High / Low Vrange          1.2 / 2.4      1.4 / 2.8   ARMS
   find in our applications group also              Peak Current         High / Low Vrange          3.0 / 6.0      3.0 / 6.0   Apeak
   permeates our modern manufac-           Protection
                                                    Adj. Current limit   Resolution                                      0.1   A RMS
   turing facility where our products               Modes                               Const. Voltage or Const. Current
                                                    Over Temperature and Over Voltage                                      
   are carefully built. No unit leaves
                                           Input
   our factory without being thor-                  Connection                                 Rear panel terminal block
                                                    Line Voltage         2 wire + GND          100, 115, 200, 230 ± 10%        V RMS
   oughly tested to ensure quality, re-             Line Current                                                       < 16    A RMS
   liability and conformance to speci-              Line Frequency                                                 47 - 440    Hz
                                                    Holdup Time                                                           10   ms
   fications.                              Measurements        (* Requires Option -OP1)
                                                    Current              Range                                        4.000    A RMS
   Power Ratings:                                                        Accuracy                 0.2 % FS + 0.3 % rdng
                                                                         Resolution                            0.001 / 0.01    A RMS
     The 351TL is rated for 350 VA                  Peak Current*        Range                                        12.00    A
                                                                         Accuracy                 0.5 % FS + 0.5 % rdng
   of power down to 90 % of voltage                                      Resolution                               0.01 / 0.1   A
   range. The 251TL is rated for 250                Voltage*             Range                                    0 - 300.0    V RMS
                                                                         Accuracy               0.1 % FS + 0.05 % rdng
   VA of power down to 78 % of volt-                                     Resolution                                      0.1   V RMS
                                                    Power*               Range                                        400.0    W
   age range.                                                            Accuracy                                 0.5 % FS
                                                                         Resolution                                      0.2   W
                                                    Power Factor*        Range                                  0.00 - 1.00
                                                                         Resolution                                    0.01
                                           Remote Control (* Requires Option -OP1)
                                                    Interface*                                    RS232C and IEEE-488
                                                                         IEEE Functions           SH1, AH1, T8, L3, RL2
                                                                         RS232C settings                       19200,8,n,1
                                                                         Command Language                              SCPI
                                                    Remote Inhibit*      Output shut down               TTL in, active low     BNC
                                                    Function Strobe*     On V or F change              TTL out, active low     BNC
                                           Physical
                                                    Dimensions           HxWxD                              5.25 x 19 x 22     inches
                                                                         HxWxD                            133 x 483 x 560      mm
                                                    Weight (net)                                                    75 / 34    lbs / kg
                                                    Vibration and Shock                      Designed to meet NSTA-1A
                                                    Temperature          Operating                                  0 to 40    °C
V-F Rating chart
                                                                         Storage                               - 40 to + 85    °C
                                          Note: Specifications shown are valid over an ambient temperature range of 25°±5°C.
     Remote Control Option                        Supplied with:                                   Customer Support
       The TL Series can be ordered                · User and Programming Manual                      For technical support and ser-
     with option package 1 (-OP1) to add             on CD ROM                                     vice, or to discuss your AC power
     a combined RS232C and IEEE-                   · WindowsTM Graphical User                      application needs, contact Califor-
     488 remote control interface. Front             Interface (with -OP1 option)                  nia Instruments Corp. or your local
     panel and bus measurements are                · RS232C Serial Cable (with -                   representative.
     included with this option.                      OP1 option)
                                                                                                   CE Mark
     Ordering Information                                                                             The TL Series has been fully
     Models:                                                                                       tested for compliance with all appli-
     351TL 350 VA linear AC Source                                                                 cable CE Mark requirements.
     251TL 250 VA linear AC Source
     Options:
     -EXT    External Oscillator Input.
             (Removes internal
             oscillator)
     -L22    Locking knobs
                                                  Higher Power Switchers
     -OP1    Option package 1:                      For applications requiring more
             · Measurements                       than 350 VA of output power, the
             · IEEE-488 / RS232C                  RP Series of AC switchers offer
             Interface and GUI                    power levels of 800 to 2000 VA .
             software                             These models are housed in a 3.5
             · Remote Inhibit input               inch or 5.25 inch high rackmount en-
             · Function Strobe output             closures. Refer to the 801RP/
     -RMS    Rack Mount Slides                    1251RP , 2001RP and 2003RP
                                                  data sheets for details.




      351TL and 251TL Dimensions




                                                                                                    Contact California Instruments:
                                                                                                               CompuMess Elektronik GmbH
                                                                                                      Lise-Meitner-Str. 1 · D-85716 677-9040
                                                                                                                                858 Unterschleißheim
                                                                                                    Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
                                                                                                                       FAX:·858 677-0940
                                                                                                        info@compumess.de www.compumess.de
                                                                                                            Email: sales@calinst.com
                                                                                                                www.netzteile.de
                                                                                                     Web page: http://www.calinst.com


9689 Towne Centre Drive, San Diego, CA 92121-1964                         (858) 677-9040                               FAX : (858) 677-0940
© Copyright 2005, California Instruments Corp.   Specifications subject to change without notice      Printed in the USA.           DS TLS 10/05