CE-150 SERIES OUTPUT SPECIFICATIONS
Features Total Output Power 100W Convection cooled
125W Convection Cooled
Universal 85-264 VAC Input w/1Sq.ft. Baseplate
High Efficiency 150W 300 LFM Forced Air
Compact 4.0" X 7.0" X 1.75" Size Output Voltage Output 1: ±0.25%
Centering Output 2: ±0.25% (X0XX)
2 Year Warranty
±3.0% (X1XX)
One to Four Tightly Regulated Outputs Output 3: ±2.0%
EN 60950 ITE Certification Output 4: ±2.0%
EN 60601-1 Medical Certification (All outputs at 50% load)
Class B Emissions Per EN 55011/22 Source Regulation Outputs 1-4: 0.5%
Harmonic Current per EN 61000-3-22 Load Regulation Output 1:0.5% (0-100% Load
EMC to EN 61000-6-2 & EN 60601-1-12 Change)
Output 2:
Optional Perforated Cover
(X0XX) 0.5% (0-100%
Load Change)
(X1XX) 3.0% (10-100%
Load Change)
Output 3: 2.0% (10-100%
Load Change)
Output 4: 2.0% (0-100%
Load Change)
Cross Regulation Output 2: 0.5% (X0XX)
5.0% (X1XX)
Output 3: 2.0%
Output 4: 2.0%
(Output 1 load varied
50-100%))
Output Voltage AdjustOutput1-2:95%-105%(X0XX)
Range Output 1: 95%-105% (X1XX)
INPUT SPECIFICATIONS Output 1: 85%-105%
Source Voltagee 85-264 Voltage AC (1001,4001)
Frequency Range 47-63 Hz Output 2: 85%-105%
Source Current (4002,4003)
True RMS 3A At 85V Inputut Output Noise Outputs 1-4: 1%
Peak Inrush 30A Turn On Overshoot None
Peak Repetive 4.25A at 85V Input Transient Response Outputs 1-4:
Harmonic Distortion 0.05 Volt. Deviation 5.0%
Efficiency .68 -.80 (Varies by model) Recovery Time 500ÂFS
Power Factor 0.90 (150 watts, 230V) Load Change 50% To 100%
ENVIRONMENTAL SPECIFICATIONS Output Overvoltage Output 1: 110% to 150%.
Ambient 0°C to +70°C Derating: See Protection (Optional) Shuts down all
Operating Power Rating Chart 0°C to outputs. Cycle
Temperature +50°C Derating: See Power input to restart
Range Rating Chart Output Overpower 165 W Min.,Outputs 1 and 2
Protection Outputs cycle on/off, auto
Ambient
recovery
Storage
-40°C to +85°C Output Overcurrent 110% Min., Outputs 3 and4
Temperature
Protection
Range
Hold Up Time 20 mS Min, 150 W Output
Temperature Outputs 1-4: 0.02%/°C Outputs 120 V Inputt
Coefficientt 1-4: 0.02%/°C Start Up Time 3 Seconds
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
SAFETY SPECIFICATIONS GENERAL SPECIFICATIONS
General Protection Class: I Dielectric Strength
Reinforced Insulation 5656 VDC, Primary to
Overvoltage Category: II Secondary, 1 Sec.
Basic Insulation 2121 VDC, Primary to
Pollution Degree: 2 Ground, 1 Sec.
Operational Insulation 707 VDC, Secondary to
Ground, 1 Sec.
Underwriters UL 60950, Third Edition UL
Laboratories 2601 - 1 Second Edition CB Leakage Current <300ÂFA Earth Leakage
File E137708 Report Per IEC 950 (1991) Current
Second Edition A1, A2, A3, Power Fail Signal Logic low with input power
A4 All EN 60950 Deviations (Optional) failure 10 mS minimum
CB Report Per IEC prior to output 1 dropping
601-1-1988 First Edition, A1, 1%
A2 Remote On/Off (Optional)Contact closure shuts off all
outputs
UL CAN/CSA-C22.2 No.
Remote Sense (Single 250mV compensation of
Recognition 60950:00
Models ) output cable losses
Mark for CAN/CSA-C22.2 No.
Mean-Time Between 150,000 Hours min.,
Canada 601-1-M90
Failures MIL-HDBK-217F, 25° C,
File E137708
GB
TUV EN 60950:2000 Weight 2.0 Lbs.
EN 60601-1/A2:1995
Low Voltage Directive
MODEL LISTING
Model Output 1 Output 2 Output 3 Output 4
CE-150-4001 +3.3/15A +5V/5A +12V/2A -12V/2A
CE-150-4002 +5V/15A +3.3V/5A +12V/2A -12V/2A
CE-150-4003 +5V/15A +3.3V/5A +15V/2A -15V/2A
CE-150-4004 +5V/15A -5.2V/5A +12V/2A -12V/2A
CE-150-4005 +5V/15A -5.2V/5A +15V/2A -15V/2A
CE-150-4006 +5V/15A +12V/5A +12V/2A -12V/2A
CE-150-4007 +5V/15A +12V/5A +15V/2A -15V/2A
CE-150-4101 +5V/15A +24V/5A +12V/2A -12V/2A
CE-150-4102 +5V/15A +24V/5A +15V/2A -15V/2A
CE-150-3001 +5V/15A +12V/5A -12V/2A
CE-150-3002 +5V/15A +15V/5A -15V/2A
CE-150-3003 +15V/5A -15V/5A +5V/2A
CE-150-2001 +12V/7.5A -12V/5A
CE-150-2002 +15V/5A -15V/5A
CE-150-2003 +5V/15A +12V/6A
CE-150-2101 +5V/15A +24V/5A
CE-150-1001 3.3V/30A (5)
CE-150-1002 5V/30A (5)
CE-150-1003 12V/12.5A
CE-150-1004 15V/10A
CE-150-1005 24V/6.25A
CE-150-1006 28V/5.4A
CE-150-1007 48V/3.1A
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
Notes
Consult factory for alternate output configuration.
Consult factory for positive, negative or floating outputs.
Refer to Application Information for complete output power ratings.
All specifications are maximum at 25° C unless otherwise stated and are subjected to change without
notice.
Specify optional power fail, overvoltage protection or remote on/off when ordering.
UL, CUL only:CE-150-4008, TUV only:CE-150-4011
CE-150 SERIES MECHANICAL SPECIFICATIONS
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
APPLICATIONS INFORMATION
1. Each output can deliver its rated current but 15. This product was type tested and safety
total output power must not exceed 100, 125 or certificated using the the dielectric strength
150 watts as determined by the cooling method. test voltages listed in Table V of UL 60601-1.
2. Rated 20 amps maximum when convection In consideration of clause 20.4g, care must be
taken to insure the voltage applied to a
cooling only.
reinforced insulation does not over stress basic
3. Free air convection cooling, 100 watts insulation. Secondary to ground capacitors
maximum output power. may need to be removed prior to performing a
4. Base plate cooled rating of 125 watts requires a dielectric strength type test on the end
one square foot .09" thick aluminum area product. It is highly recommended that the DC
attached to bottom four mounting holes. test voltages listed in DVB.1. Annex DVB are
5. Forced air cooling rating of 150 watts requires not exceeded during a production-line
an air speed of 300 linear feet per minute dielectric strength test of the assembled end
product. Please consult factory for further
flowing past a point one inch above the main
information.
isolation transformer.
16. Maximum screw penetration into bottom
6. Semiconductor case temperature must not chassis mounting holes is .187 inches.
exceed 110 ° C.
7. Sufficient area must be provided around Maximum Output Power vs. Ambient
convection cooled power supplies to allow Temperature
natural movement of air develop.
8. 300 linear feet per minute of airflow must be
maintained one inch above any point of the
heatsink in the direction shown when forced air
cooling is required.
9. This product is intended for use as a
professionally installed component within
information technology and medical equipment.
10. A minimum load of 10% is required on output
one to insure proper regulation of remaining
outputs.
11. Remote sense terminals may be used to
compensate for cable losses up to 250mV. The
CONNECTOR SPECIFICATIONS
use of a twisted pair is recommended as well as
.156 friction lock header
a decoupling capacitor (0.1 0 10µF) and a
mates with Molex
capacitor of 100µF/amp connected across the 09-50-3031 or equivalent
load. P1 AC Input
crimp terminal housing
12. Peak to peak output ripple and noise is with Molex 2478 or
measured directly at the output equivalent crimp terminal.
terminals of the power supply, without the use 6-32 screw down terminal
of the probe ground lead or retractable tip, 20 mates with #6 ring
P2 DC Output(Single)
MHz bandwidth. tongue terminal.(10 in-lb
13. This product includes only one fuse in the input max)
circuit. In consideration of Clause 57.6 of UL .156 friction lock header
2601-1, a second fuse may be required in the mates with Molex
09-50-3121 or equivalent
end product. P2 DC Output(Multiple)
crimp terminal housing
14. This power supply has been safety approved and with Molex 08-50-0189 or
final tested using a DC dielectric strength test.
equivalent crimp terminal.
Please consult factory before performing AC .187 quick disconnect
dielectric strength test. G Ground
terminal.
.100 friction lock header
RECOMMENDED AIR FLOW DIRECTION mates with Molex
1.Optimum 2.Good 3.Fair 22-01-2067 or equivalent
P3 Option/Sense(Single)
crimp terminal housing
with Molex type 6459 or
equivalent crimp terminal.
.100 friction lock header
mates with Molex
Option/Sense(Multiple) 22-01-2047 or equivalent
P3
crimp terminal housing
with Molex type 6459 or
equivalent crimp terminal.
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de