DR-120 Series
Low Cost, Industrial
120W, DIN Rail Mount New Industrial
AC/DC Power Supplies Supplies!!
Electrical Specifications
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
Input
Parameter Conditions Min. Typ. Max. Units
Key Features: 88 132
VAC
· 120W Output Power Input Voltage Range AC Input Selected by Switch On Front Panel 176 264
· DIN Rail Mountable 248 370 VDC
· Selectable AC Input Input Frequency Range 47 63 Hz
· UL 508 Approved 230 VAC, Cold Start 40
Inrush Current A
115 VAC, Cold Start 20
· Safety Approved
Leakage Current 240 VAC 3.5 mA
· 12, 24 & 48 VDC Outputs Output
· Cond./Rad. EMI Class B Parameter Conditions Min. Typ. Max. Units
· >136 kH MTBF Output Voltage Tolerance Note 1 ±1.0 %
· LOW COST! 12 VDC Output 12 14
Voltage Adjustment Range 24 VDC Output 24 28 VDC
48 VDC Output 48 53
Line Regulation ±0.5 %
Load Regulation Iout = 10% to 100% ±1.0 %
Set Up Time At Full Load 500 mSec
Rise Time At Full Load 70 mSec
230 VAC, Full Load 36
Hold Time mSec
115 VAC, Full Load 32
12 VDC Output 80
Ripple & Noise (Note 2) 24 VDC Output 80 mV Pk-Pk
48 VDC Output 100
Output Power Protection Note 3 105 150 %
12 VDC Output 15 16.5
Over Voltage Protection (Note 4) 24 VDC Output 29 33 VDC
48 VDC Output 58 65
12 VDC Output 80 85 90
Over Temperature Protection (Note 5) ºC
24 & 48 VDC Output 85 90 95
Temperature Coefficient 0ºC to 50ºC ±0.03 %/ºC
Switching Frequency Fixed 55 kHz
General
Parameter Conditions Min. Typ. Max. Units
Input - Output 3,000
Isolation Voltage Input - FG (Frame Ground) 1,500 VAC
RoHS Compliant Output - FG (Frame Ground) 500
Isolation Resistance (Note 6) 500 VDC 100 M
MicroPower Direct Environmental
232 Tosca Drive Parameter Conditions Min. Typ. Max. Units
Stoughton, MA 02072 Operating Temperature Range -10
Ambient +25 +60 ºC
USA Storage Temperature Range -20 +85 ºC
Operating Humidity RH, Non-condensing 20 90 %
T: (781) 344-8226 Storage Humidity RH, Non-condensing 10 95 %
F: (781) 344-8481 Vibration 10 ~ 500 Hz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour
E: sales@micropowerdirect.com Physical
W: www.micropowerdirect.com Case Size 2.60 x 4.93 x 3.94 Inches (65.5 x 125.5 x 100.0 mm)
Case Material Aluminum
Connection Screw Terminal
Weight 28 Oz (0.79 kg)
Reliability Specifications
Parameter Conditions Min. Typ. Max. Units
MTBF MIL HDBK 217F, 25ºC, Gnd Benign 136.8 kHours
Safety Standards UL 508, UL 60950, EN 60950-1
Safety Approvals UL, cUL, TUV
EMI Compliance Compliance to EN55011, EN55022 (CISPR22) Class B
Harmonic Current Compliance Compliance to EN6100-3-2,-3
EMS Immunity Compliance EN6100-4-2,3,4,5,6,8,11; ENV50204;EN6100-6-2(EN50082-2) Heavy Ind. Level, criteria A
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
Model Selection Guide
Input Output
Rated Fuse Rating
Model Efficiency
Power Voltage (VAC) Current (A) Voltage Current (A) Current (A) Slow-Blow
Number (%, Typ)
(W) (VDC) Max) Range (A)
Range 115 VAC 230 VAC
DR-120-12 120 88 - 132 / 176 - 264 2.6 1.6 12 10.0 0 ~ 10.0 80 5.0
DR-120-24 120 88 - 132 / 176 - 264 2.6 1.6 24 5.0 0 ~ 5.0 84 5.0
DR-120-48 120 88 - 132 / 176 - 264 2.6 1.6 48 2.5 0 ~ 2.5 85 5.0
Notes:
1. Output voltage tolerance includes set-up tolerance, line regulation and
load regulation. For the 12V output model, tolerance is ±2.0%.
Derating Curve - Output Power vs Ambient Temperature
2. Ripple & noise is measured using equipment with 20 Mhz of bandwidth.
Connection to the unit under test is made with a 12 inch length of "twisted
pair" wires terminated with a set of 1.0 µF & 4.7 µF capacitors connected
in parallel.
3. Overload protection is foldback current limiting. The unit recovers auto-
matically when the fault is removed.
4. Over voltage protection is a clamp type. The power to the unit must be
manually reset to recover.
5. Over temperature protection shuts down the output. The unit recovers
automatically when the temperature goes down. The thermal detector
is mounted on the heat sink of the power semiconductor.
6. Isolation resistance is given for Input/Output; Input/FG and Output/FG.
7. To mount the unit to the DIN rail, tilt the unit rearwards from the top,
fitting the mount over the top of the rail. Press back on the bottom front
of the unit until it locks in place on the rail. To remove the unit from the
rail, pull the removal clip at the bottom rear of the unit downward with
a screw driver. With the clip down, lift up on the unit from the bottom
front until it clears the rail. Before installation or removal all wiring should
be disconnected and the main power to the system shut off.
8. When wiring the supply, all lines should be as thick and short as possible.
AWG 14 wire is recommended for the DR-120 series.
9. The units should be mounted so they are vertically orientated. Air flow
(if it is provided) would optimally flow from the bottom to the top of Static Characteristics (24 Vout)
the unit.
10. It is recommended that a fuse be used on the input of a power supply
for protection. See the table above for the correct rating.
Mechanical Dimensions
Terminal Connections - TB1
Pin Function
1 Frame Ground (FG)
2 AC/Neutral (DC+)
3 AC/Live (DC-)
Terminal Connections - TB2
Pin Function
1,2 DC Output (+V)
3,4 DC Output (-V)
Mechanical Notes:
· All dimensions are typical in inches (mm)
· Tolerance x.xx = ±0.01 (±0.25)
MicroPower Direct
www.micropowerdirect.com GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
CompuMess Elektronik
232 Tosca Drive Stoughton, MA 02072 · TEL: (781) 344-8226Telefon
· FAX: 15 01 - 0 · Telefax ·(089) 32 15 01 - 11
(089) 32 (781) 344-8481 E-Mail: sales@micropowerdirect.com
info@compumess.de · www.compumess.de · www.netzteile.de