Infratek ITL-101 Universal Power Transmitters DC-50kHz

The Model ITL101 Broad Band Power Transmitters can be tailored to your needs and are
suitable for DC, 50/60/400Hz power line, frequency inverter, and other electronic drives.


Features At A Glance

  ·      Suitable for DC, power lines, inverters
  ·      1-, 2-, 3-, and multi-phase
  ·      Isolated channels each phase (3000V)
  ·      DC-50kHz, Option DC-100kHz
  ·      Fast response output for process control
  ·      Outputs: ±20mA / ±5V for power, 3600
         Pulses / hour for energy
  ·      0.2 % accuracy
  ·      Wide voltage range 10V-600V
  ·      Wide current range 10mA-20A, extend-
         able to 3000A
  ·      Multi-phase: two outputs for power




Yields Correct Power For Any Wave Form
The ITL101 Broad Band DC-50kHz Power Transmitters are available as single-phase, 2-phase (ARON), 3-
phase, and multi-phase versions (e.g. channel 1/2 in ARON, 0-20mA output; channel 3 for DC-power, 0-5V
output). In addition to the standard current- and voltage ranges special ranges for current 10mA-20A, and
voltage, 10V-600V, can be supplied. 3000Vac channel to channel ­ and channel to output isolation results in
maximum freedom for input connections. The ITL101 withstands fast common mode transients and can be
used in frequency inverters and other electronically switched loads.
Available options are: DC-100kHz, non-standard voltage range, non-standard current range, 40ms response
output for process control, energy output (3600 pulses per hour for full scale), bipolar output to measure
recuperated power, and single- and three phase 0-100A current sensors.


Specifications ITL101

      Voltage ranges Un           ITL101-1/3: 120V, 250V; ITL101-2/4: 200V, 400V; working range: 0-150 %; DC-50kHz
      Current ranges In           ITL101-1/2/3/4: 1A, 2A, 5A, 10A, 20A; working range: 0-150 %; DC-50kHz
      Power ranges                ITL101-1: voltage x current; ITL-101-2: 2 x voltage x current;
                                  ITL101-3: 3 x voltage x current; corresponds to 20mA or 5V.
      Power Accuracy              40-400Hz: 0.1 % reading +0.2 % range (0.2 % typical) 0