Hier Klicken für das PDF Dokument!!!

                   25 WATTS
                                                 NO MINIMUIM ORDER REQUIRED
                SRP-25 SERIES                      OUTPUT SPECIFICATIONS

Features                                       Total Output Power      25 W (20W, 1001)
                                               Output Voltage          Output 1: +/-0.25%
     Universal 85-264 VAC Input                Centering               Output 2: +/-5.00%
     High Efficiency                                                   Output 3: +/-2.00%
     Advanced SMT Design                                               (All outputs at 50% rated
                                                                       load)
     Compact 2.25" X 4.00" X .96" Size
                                               Source Regulation       Outputs 1-3: 0.5%
     Class B Emissions Per EN 55022/11         Load Regulation         Outputs 1: 0.5% (0-100%
     EMC to EN 61000-6-2 & EN 60601-1-2                                Load Change)
     2 Year Warranty                                                   Output 2: 5.0% (10-100%
     Fits 1U Application                                               Load Change)
     EN 60950 ITE Certification                                        Output 3: 1.0% (0-100%
     EN 60601-1 Medical Certification                                  Load Change)
                                                                       Output 2:(2003) 6.0%
     Optional Chasis & Cover
                                                                       (30-100% Load Change)
                                               Cross Regulation        Output 2: 5.0%
                                                                       Output 3: 2%
                                                                       (Output 1 load varied
                                                                       50-100%)
                                               Output Voltage Adjust    Output 1: 95% to 105%
                                               Output Noise            Outputs 1-3: 1%
                                               Turn On Overshoot       None
                                               Transient Response      Outputs 1-3
                                               Volt. Deviation         5%
                                               Recovery Time           1 mS
                                               Load Change             50% To 100%
                                               Output Overvoltage      Output 1: 110% to 150%
                                               Protection (Optional)
                                               Output Overpower        Output 1&2 110% Min.
                                               Protection              Outputs cycle on/off, auto
                                                                       recovery
                                               Output Overcurrent      Output 3     110% Min.
                                               Protection
                                               Hold Up Time            10 mS Min, 25 W Output
                                                                       120 V Input
                                               Start Up Time           1 Second




       INPUT SPECIFICATIONS                       ENVIRONMENTAL SPECIFICATIONS
Source Voltage    85-264 Voltage AC            Ambient Operating 0 oC to +70oC Derating:
Frequency Range   47-63 Hz                     Temperature Range See Power Rating Chart
Source Current                                 Ambient Storage
True RMS          8A At 85V Input                                       -40 oC to +85oC
                                               Temperature Range
Peak Inrush       30A                                                                     o
Efficiency        .66 -.72 (Varies by model)   Temperature Coefficient Outputs 1-3: 0.02%/ C




                 CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                     Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
     SAFETY SPECIFICATIONS                                  GENERAL SPECIFICATIONS
General                  Protection Class:           I Dielectric Strength
                                                            Reinforced Insulation5656 VDC, Primary to
                          Overvoltage Category:      II                           Secondary, 1 Sec.
                                                                  Basic Insulation2121 VDC, Primary to
                                                                                  Ground, 1 Sec.
                          Pollution Degree:          2
                                                        Operational Insulation 707 VDC, Secondary to
                                                                                  Ground, 1 Sec.
        Underwriters      UL 60950, Third Edition       Leakage Current           <300 ÂIA Earth Leakage
        Laboratories      UL 2601 - 1 Second                                      Current
        File E137708      Edition
                                                        Mean Time Between         100,000 Hours min.,
                          CB Report Per IEC 950
                                                        Failures                  MIL-HDBK-217F, 25oC, GB
                          (1991)                        Weight                    0.62 Lbs. Chassis and
                          Second Edition A1, A2, A3,                              Cover
                          A4
                                                                                  0.30 Lbs. Open Frame
                          All EN 60950 Deviations
                                                                ELECTROMAGNETIC COMPATIBILITY
                          CB Report Per IEC                                SPECIFICATIONS
                          601-1-1988
                          First Edition, A1, A2
                                                        Electrostatic      EN 61000-4-2 +/-8kV Contact
        UL Recognition CAN/CSA-C22.2 No.                Discharge                         Discharge
        Mark for          950-M95
                                                                                          +/-8kVAir
        Canada            CAN/CSA-C22.2 No.
                                                                                          Discharge
        File E137708      601-M90                       Radiated            EN 61000-4-3 80MHz-2.5GHz,
        TUV               EN 60950/A11:1997             Electro-magnetic                  10V/m, 80% AM
                          EN 60601-1/A2: 1995           Field
                          Low Voltage Directive         EFT/Bursts         EN 61000-4-4 +/-2kV
                                                        Surges              EN 61000-4-5 +/-1 kV Differential
                                                                                          Mode
                                                                                          +/-2 kV Common
                                                                                          Mode
               Notes                                    Conducted           EN 61000-4-6 .15-80MHz., 10V,
Consult factory for alternate output configuration.     Immunity                          80% AM
Consult factory for positive, negative or floating      Voltage Dips and EN               30% Reduction
output 2 or 3.                                          Intuptions          61000-4-11    95% Reduction
Refer to Application Information for complete output                                     60% Reduction
power ratings.                                                                           95% Reduction
All specifications are maximum at 25C unless           Radiated          EN 55011/22 Class B
otherwise stated and are subjected to change           Emissions
without notice.                                        Conducted         EN 55011/22 Class B
Specify optional chassis nad cover when ordering.      Emissions
                      MODEL LISTING
 Model                      Output 1                   Output 2                  Output 3
 SRP-25-3001                +5V/3A                     +12V/1.5A                 -12V/.5A
 SRP-25-3002                +5V/3A                     +15V/1.5A                 -15V/.5A
 SRP-25-2001                +5V/3A                     +24V/1A
SRP-25-2002                +5V/3A                      +12V/1.5A
SRP-25-2003                +5V/3A                      -5V/2A
SRP-25-2004                +12V/1.5A                   -12V/1.5A
SRP-25-2005                +15V/1.5A                   -15V/1.5A
SRP-25-1001                3.3V/6A
SRP-25-1002                5V/5A
SRP-25-1003                12V/2.08A
SRP-25-1004                15V/1.67A
SRP-25-1005                24V/1.04A
SRP-25-1006                48V/0.52A




                   CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                       Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
SRP-25 SERIES MECHANICAL SPECIFICATIONS




        CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
            Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
   Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
      APPLICATIONS INFORMATION
1. Each output can deliver its rated current but           10. Maximum screw penetration into bottom
     total output power must not exceed                         chassis mounting holes is .100 inches.
     25 watts.                                             11. Maximum screw penetration into side chassis
2.   Semiconductor case temperature must not                    mounting holes is .250 inches.
     exceed 110 oC                                         12. To meet emissions specifications, all four
3.   Sufficient area must be provided around                    mounting hole ground pads must
     convection cooled power supplies to allow                  be electrically connected. Use metal standoffs
     natural movement of air develop.                           attached to a common metal chassis or base
4.   This product is intended for use as a                      plate.
     professionally installed component within
     information technology and medical equipment.                Maximum Output Power vs. Ambient
5.   A minimum load of 10% is required on output                                 Temperature
     one to insure proper regulation of
     remaining outputs.
6.   Peak to peak output ripple and noise is
     measured directly at the output
     terminals of the power supply, without the use
     of the probe ground lead or retractable tip, 20
     MHz bandwidth.
7.   This product is use only one fuse in the input
     circuit. In consideration of clause 57.6 of UL
     2601-1, a second fuse may be required in the
     end product.
8.   This product was type tested and safety
     certificated using the the dielectric strength test
     voltages listed in Table V of UL 60601-1. In
     consideration of clause 20.4g, care must be                 CONNECTOR SPECIFICATIONS
     taken to insure the voltage applied to a                        .156 friction lock header mates with Molex
     reinforced insulation does not over stress basic P1AC           09-50-3031 or equivalent crimp terminal
     insulation. Secondary to ground capacitors may         Input housing with Molex 08-50-0189 or
     need to be removed prior to performing a                        equivalent crimp terminal.
     dielectric strength type test on the end product.               .156 friction lock header mates with Molex
     It is highly recommended that the DC test              DC       09-50-3061 or equivalent crimp terminal
                                                         P2
     voltages listed in DVB.1. Annex DVB are not            Output housing with Molex 08-50-0189 or
     exceeded during a production-line dielectric                    equivalent crimp terminal.
     strength test of the assembled end product.         G Ground .187 quick disconnect terminal.
     Please consult factory for further information.           RECOMMENDED AIR FLOW DIRECTION
9.   This power supply has been safety approved and 1. Optimum
     final tested using a DC                                 2. Good
     dielectric strength test. Please consult factory        3. Fair
     before performing AC dielectric strength test.




                  CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                       Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de