Hier Klicken für das PDF Dokument!!!

                    100 WATTS
                                                        NO MINIMUIM ORDER REQUIRED
                 SRW-100 SERIES                            OUTPUT SPECIFICATIONS

Features                                              Total Output Power    70W Convection Cooled
                                                      at 50o C              85W Convection Cooled w/1
      Universal 85-264 VAC Input                                            Sq.ft. baseplate
      High Efficiency                                                       100W LFM Foreced Air
      Compact 3.3" X 5" X 1.5" Size                   Output Voltage        Output 1:         +/-0.25%
                                                      Centering             Output 2:(SRW) +/-0.25%
      Class B Emissions Per EN 55022/11
                                                                                       (SRP) +/-5.0%
      EMC to EN 61000-6-2 & EN 60601-1-2                                    Output 3:         +/-2.0%
      2 Year Warranty                                                       Output 4:         +/-2.0%
      One to Four Tightly Regulated Outputs                                 (All outputs at 50% rated load)
      EN 60950 ITE Certification                      Source Regulation     Outputs 1-4: 0.5%
      EN 60601-1 Medical Certification                Load Regulation       Output 1:0.5% (10-100% Load
      Optional Perforated Cover                                             Change)
                                                                            Output 2: (SRW) 0.5%
                                                                                          (10-100% Load
                                                                                          Change)
                                                                                          (SRP) 5.0%
                                                                                          (10-100% Load
                                                                                          Change)
                                                                            Output 3: 1.0% (10-100%
                                                                            Load Change)
                                                                            Output 4: 1.0% (20-100%
                                                                            Load Change)
                                                      Cross Regulation      Output 2: (SRW)         Output 1
                                                                                          0.2%     load
                                                                                          (SRP)    varied
                                                                                          5.0%     50-100%
                                                                            Output 3:           0.2%
       GENERAL SPECIFICATIONS                                               Output 3:           0.2%
Dielectric Strength                                   Output Voltage         Output 1: 95-105%
        Reinforced Insulation5656 VDC, Primary to     Adjust Range                       85-105%
                              Secondary, 1 Sec.                             (1001,1004)
                        Basic 2121 VDC, Primary to                           Output 2: 95-105% (SRW
                    InsulationGround, 1 Sec.                                models only)
       Operational Insulation707 VDC, Secondary to Output Noise             Outputs 1-4: 1%
                              Ground, 1 Sec.          Turn On Overshoot None
Leakage Current               <500 ÂHA Earth LeakageTransient Response Outputs 1-4
                              Current                                       Voltage Deviation 5.0%
Power Fail Signal             Logic low with input                          Recovery Time       2mS
(optional)                    power failure 2mS                             Load Change        50% to 100%
                              minimum prior to output Output Overvoltage Output 1: 110% to 150%
                              1 dropping 1%           Protection (Optional)
Remote Sense (single          250mV compensation of Output Overpower        Outputs 1 & 2:      110% Min
output models only)           output cable losses     Protection            Outputs cycle on/off, auto
Mean Time Between Failures150,000 Hours min.,                               recovery
                              MIL-HDBK-217F, 25oC, Output Overcurrent Outputs 3 & 4:            110% Min
                              GB                      Protection
Weight                        1.00 Lbs. Chassis       Hold Up Time          10 mS min., 100W, 120V Input
                              1.05 Lbs. Chassis/CoverStart Up Time           1 Second
        INPUT SPECIFICATIONS                               ENVIRONMENTAL SPECIFICATIONS
Source Voltage        85-264 Volts AC                 Ambient Operating           0 oC to +70oC Derating:
Frequency Range       47-63 Hz                        Temperature Range           See Power Rating Chart
SourceCurrent                                         Ambient Storage Temp.
                                                                                -40 oC to +85oC
True RMS             3A at 85V Input                  Range
Peak Inrush                                                                                      o
                     30A                              Temperature Coefficient Outputs 1-4: 0.02%/ C
Efficiency           .68-.84 (Varies by model)




                   CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                       Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
         ELECTROMAGNETIC COMPATIBILITY
Electrostatic Discharge                      EN 61000-4-2          +/-8kV Contact Discharge
                                                                   +/-8kVAir Discharge
Radiated Electro-magnetic Field              EN 61000-4-3          80MHz-2.5GHz, 10V/m, 80% AM
EFT/Bursts                                   EN 61000-4-4          +/-2kV
Surges                                       EN 61000-4-5          +/-1 kV Differential Mode
                                                                   +/-2 kV Common Mode
Conducted Immunity                           EN 61000-4-6          .15-80MHz., 10V, 80% AM
Voltage Dips and Interruptions               EN 61000-4-11         30% Reduction
                                                                   95% Reduction
                                                                   60% Reduction
                                                                   95% Reduction
Radiated Emissions                           EN   55011/22         Class B
Conducted Emissions                          EN   55011/22         Class B
Harmonic Current Emissions                   EN   61000-3-2
Voltage Fluctuations and Flicker             EN   61000-3-3
                    MODEL LISTING
Model NO.                  Output 1                    Output 2          Output 3         Output 4
SRW-100-4001               +3.3V/10A(2)                +5V/4A            +12V/2A (3)      -12V/1A
SRW-100-4002                   +5V/10A(2)              +24V/2A           +12V/2A (3)      -12V/1A
SRW-100-4003                   +5V/10A(2)              +24V/2A           +15V/2A (3)      -15V/1A
SRW-100-4004                   +5V/10A(2)              -5.2V/4A          +12V/2A (3)      -12V/1A
SRW-100-4005                   +5V/10A(2)              -5.2V/4A          +15V/2A (3)      -15V/1A
SRW-100-4006                   +5V/10A(2)              +3.4V/4A          +9V/1A           24V/0.5A
SRW-100-4007                   +5V/10A(2)              +15V/3A           +12V/2A (3)      -12V/1A
SRW-100-4008                   +5V/10A(2)              3.3V/4A           +12V/2A (3)      -5V/1A
SRW-100-4009-IT                +3.3V/10A(2)            +5V/4A            +12V/2A (3)      -5V/1A
SRW-100-4010                   +5V/5A                  +15V/4A           +12V/2A (3)      9V/2.5A
SRW-100-4011                   +5V/10A(2)              -15V/2.2A         +15V/2.2A (3)    12V/1A
SRW-100-4012                   +5V/10A(2)              3.3V/4A           +12V/2A (3)      -12V/1A
SRW-100-3001                   +5V/10A(2)              +12V/4A                            -12V/1A
SRW-100-3002                   +5V/10A(2)              +15V/3A                            -15V/1A
SRW-100-3003                   +5V/10A(2)              +3.3V/8A                           -12V/1A
SRW-100-3004                   +3.3V/10A               +5.8V/3A                           -48V/1A
SRW-100-2001                   +12V/5A                 -12V/4A
SRW-100-2002                   +15V/5A                 -15V/3A
SRW-100-2003                   +12.5V/4A               +16V/2A
SRW-100-1001                   3.3V/20A(4)
SRW-100-1002                   5V/20A
SRW-100-1003                   12V/8.3A
SRW-100-1004                   15V/6.7A
SRW-100-1005                   24V/4.2A
SRW-100-1006                   28V/3.6A
SRW-100-1007                   48V/2.1A
SRW-100-1008                   40V/2.5A
SRP-100-4001                   +5V/12A(2)              +24V/3A           +12V/2A (3)      -12V/1A
SRP-100-4002                   +5V/12A(2)              +24V/3A           +15V/2A (3)      -15V/1A
SPR-100-4003                   +5V/12A(2)              -5V/4A            +12V/2A (3)      -12V/1A
SRP-100-4004                   +5V/12A(2)              -5V/4A            +15V/2A (3)      -15V/1A
SRP-100-4005                   +5V/12A                 +12V/3A           +8V/2A           -8V/1A
SRP-100-3001                   +5V/12A(2)              +12V/4A                            -12V/1A
SRP-100-2001                   +5V/12A(2)              +24V/3A




                  CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                          Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
                                       Notes
Consult factory for alternate output configurations.
Consult factory for positive, negative or floating outputs. Refer to Application Information for complete
output power ratings.
All specifications are maximum at 25o C unless otherwise stated and are subjected to change without
notice. Specify optional perforated cover, power fail, overvoltage protection, isolated output 2, isolated
output 4 or DC Input when ordering.
                SAFETY SPECIFICATIONS
General                             Protection Class:                                                        I

                                   Overvoltage Category:                                                     II

                                   Pollution Degree:                                                         2

          Underwriters            UL 60950, Third Edition
          Laboratories            UL 2601 - 1 Second Edition
          File E137708            CB Report Per IEC 950 (1991)
                                  Second Edition A1, A2, A3, A4
                                  All EN 60950 Deviations
                                  CB Report Per IEC 601-1-(1988)
                                  First Edition, A1, A2
          UL Recognition Mark for CAN/CSA-C22.2 No. 60950:00
          Canada                  CAN/CSA-C22.2 No. 601-1-M90
          File E137708
          TUV                     EN 60950:2000
                                  EN 60601-1/A2: 1995
                                  Low Voltage Directive
       SRW/SRP-100 SERIES MECHANICAL SPECIFICATIONS




                   CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                         Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
   Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
   Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
    APPLICATIONS INFORMATION
 1. Each output can deliver its rated current but       17. This product was type tested and safety
     total output power must not exceed 70, 85 or           certificated using the the dielectric
     100 watts as determined by cooling method.             strength test voltages listed in Table V
  2. Rated 8A with convection cooling.                      of UL 60601-1. In consideration of clause
  3. Rated 1A with convection cooling.                      20.4g, care must be taken to insure the
  4. Rated 50 watts maximum output power when               voltage applied to a reinforced insulation
                                                            does not over stress basic insulation.
     convection cooled, 70 watts when baseplate or
                                                            Secondary to ground capacitors may
     forced air cooled.
                                                            need to be removed prior to performing
  5. Free air convection cooling, 70 watts maximum
                                                            a dielectric strength type test on the
     output power.
                                                            end product. It is highly recommended
  6. Base plate cooling rating of 85 watts requires a       that the DC test voltages listed in DVB.1.
     one square foot.09 thick aluminium area                Annex DVB are not exceeded during
     attached to bottom four mounting holes.                a production-line dielectric strength
  7. Forced air cooling rating of 100 watts requires        test of the assembled end product.
     an air speed of 200 linear feet per minute             Please consult factory for
     flowing past a point one inch above the main           further information.
     isolation transformer.
  8. Semiconductor case temperatures must not                  Maximum Output Power vs. Ambient
     exceed 110o C.                                                          Temperature
  9. Sufficient area must be provided around the
     convection cooled power supplies to allow
     natural movement of air to develop.
10. This product is intended for use as
     professionally installed component within
     information technology and medical equipment.
11. A minimum load of 10% is required on output
     one to ensure proper regulation of remaining
     outputs.
12. Remote sense terminals may be used to
     compensate for cable losses up to 250mV. The
     use of twisted pair is recommended as well as a         CONNECTOR SPECIFICATIONS
     decoupling capacitor (0.1-10ÂHF) and a                                    Terminal block with 4-40
     capacitor of 100ÂHF /amp connected across the P1 AC Input                 screws on 0.325 inch centers
     load side.                                          (Single)              mates with #4 spade
13. Peak to peak output ripple and noise is                                    terminals.
     measured directly at the output                                           .156 friction lock header
     terminals of the power supply, without the use                            mates with Molex 09-50-3031
     of the probe ground lead or retractable tip, 20 P1  AC Input              or equivalent crimp terminal
     MHz bandwidth.                                      (Multiple)            housing with Molex
14.  This product includes only one fuse in the input                          08-50-0189 or equivalent
     circuit. In consideration of Clause 57.6 of UL                            crimp terminal.
     2601-1, a second fuse may be required in the                              6-32 screw down terminal
                                                      P2 DC Output(Single) mates with #6 ring tongue
     end product.
                                                                               terminal.(10 in-lb max.)
15. This power supply has been safety approved
                                                                               .156 friction lock header
     and final tested using a DC dielectric strength
                                                                               mates with Molex 09-50-3101
     test. Please consult factory before performing
                                                                               or equivalent crimp terminal
     an AC dielectric strength test.                  P2 DC Output(Multiple)
                                                                               housing with Molex
16. Maximum screw penetration into chassis                                     08-50-0189 or equivalent
     mounting holes is .125 inches.                                            crimp terminal.
                                                                               .187 quick disconnect
     RECOMMENDED AIR FLOW DIRECTION                   G Ground
                                                                               terminal.
1.Optimum 2.Good 3.Fair                                                        .100 friction lock header
                                                                               mates with Molex 22-55-2047
                                                      P3 P.F./Sense(Single) or equivalent crimp terminal
                                                                               housing with Molex 6459 or
                                                                               equivalent crimp terminal.
                                                                               .100 friction lock header
                                                         P.F./Sense(Multiple) mates with Molex 50-57-2027
                                                      P3                       or equivalent crimp terminal
                                                                               housing with Molex 6459 or
                                                                               equivalent crimp terminal.


                 CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
                      Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de