Hier Klicken für das PDF Dokument!!!
100 WATTS
NO MINIMUIM ORDER REQUIRED
SRW-100 SERIES OUTPUT SPECIFICATIONS
Features Total Output Power 70W Convection Cooled
at 50o C 85W Convection Cooled w/1
Universal 85-264 VAC Input Sq.ft. baseplate
High Efficiency 100W LFM Foreced Air
Compact 3.3" X 5" X 1.5" Size Output Voltage Output 1: +/-0.25%
Centering Output 2:(SRW) +/-0.25%
Class B Emissions Per EN 55022/11
(SRP) +/-5.0%
EMC to EN 61000-6-2 & EN 60601-1-2 Output 3: +/-2.0%
2 Year Warranty Output 4: +/-2.0%
One to Four Tightly Regulated Outputs (All outputs at 50% rated load)
EN 60950 ITE Certification Source Regulation Outputs 1-4: 0.5%
EN 60601-1 Medical Certification Load Regulation Output 1:0.5% (10-100% Load
Optional Perforated Cover Change)
Output 2: (SRW) 0.5%
(10-100% Load
Change)
(SRP) 5.0%
(10-100% Load
Change)
Output 3: 1.0% (10-100%
Load Change)
Output 4: 1.0% (20-100%
Load Change)
Cross Regulation Output 2: (SRW) Output 1
0.2% load
(SRP) varied
5.0% 50-100%
Output 3: 0.2%
GENERAL SPECIFICATIONS Output 3: 0.2%
Dielectric Strength Output Voltage Output 1: 95-105%
Reinforced Insulation5656 VDC, Primary to Adjust Range 85-105%
Secondary, 1 Sec. (1001,1004)
Basic 2121 VDC, Primary to Output 2: 95-105% (SRW
InsulationGround, 1 Sec. models only)
Operational Insulation707 VDC, Secondary to Output Noise Outputs 1-4: 1%
Ground, 1 Sec. Turn On Overshoot None
Leakage Current <500 ÂHA Earth LeakageTransient Response Outputs 1-4
Current Voltage Deviation 5.0%
Power Fail Signal Logic low with input Recovery Time 2mS
(optional) power failure 2mS Load Change 50% to 100%
minimum prior to output Output Overvoltage Output 1: 110% to 150%
1 dropping 1% Protection (Optional)
Remote Sense (single 250mV compensation of Output Overpower Outputs 1 & 2: 110% Min
output models only) output cable losses Protection Outputs cycle on/off, auto
Mean Time Between Failures150,000 Hours min., recovery
MIL-HDBK-217F, 25oC, Output Overcurrent Outputs 3 & 4: 110% Min
GB Protection
Weight 1.00 Lbs. Chassis Hold Up Time 10 mS min., 100W, 120V Input
1.05 Lbs. Chassis/CoverStart Up Time 1 Second
INPUT SPECIFICATIONS ENVIRONMENTAL SPECIFICATIONS
Source Voltage 85-264 Volts AC Ambient Operating 0 oC to +70oC Derating:
Frequency Range 47-63 Hz Temperature Range See Power Rating Chart
SourceCurrent Ambient Storage Temp.
-40 oC to +85oC
True RMS 3A at 85V Input Range
Peak Inrush o
30A Temperature Coefficient Outputs 1-4: 0.02%/ C
Efficiency .68-.84 (Varies by model)
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
ELECTROMAGNETIC COMPATIBILITY
Electrostatic Discharge EN 61000-4-2 +/-8kV Contact Discharge
+/-8kVAir Discharge
Radiated Electro-magnetic Field EN 61000-4-3 80MHz-2.5GHz, 10V/m, 80% AM
EFT/Bursts EN 61000-4-4 +/-2kV
Surges EN 61000-4-5 +/-1 kV Differential Mode
+/-2 kV Common Mode
Conducted Immunity EN 61000-4-6 .15-80MHz., 10V, 80% AM
Voltage Dips and Interruptions EN 61000-4-11 30% Reduction
95% Reduction
60% Reduction
95% Reduction
Radiated Emissions EN 55011/22 Class B
Conducted Emissions EN 55011/22 Class B
Harmonic Current Emissions EN 61000-3-2
Voltage Fluctuations and Flicker EN 61000-3-3
MODEL LISTING
Model NO. Output 1 Output 2 Output 3 Output 4
SRW-100-4001 +3.3V/10A(2) +5V/4A +12V/2A (3) -12V/1A
SRW-100-4002 +5V/10A(2) +24V/2A +12V/2A (3) -12V/1A
SRW-100-4003 +5V/10A(2) +24V/2A +15V/2A (3) -15V/1A
SRW-100-4004 +5V/10A(2) -5.2V/4A +12V/2A (3) -12V/1A
SRW-100-4005 +5V/10A(2) -5.2V/4A +15V/2A (3) -15V/1A
SRW-100-4006 +5V/10A(2) +3.4V/4A +9V/1A 24V/0.5A
SRW-100-4007 +5V/10A(2) +15V/3A +12V/2A (3) -12V/1A
SRW-100-4008 +5V/10A(2) 3.3V/4A +12V/2A (3) -5V/1A
SRW-100-4009-IT +3.3V/10A(2) +5V/4A +12V/2A (3) -5V/1A
SRW-100-4010 +5V/5A +15V/4A +12V/2A (3) 9V/2.5A
SRW-100-4011 +5V/10A(2) -15V/2.2A +15V/2.2A (3) 12V/1A
SRW-100-4012 +5V/10A(2) 3.3V/4A +12V/2A (3) -12V/1A
SRW-100-3001 +5V/10A(2) +12V/4A -12V/1A
SRW-100-3002 +5V/10A(2) +15V/3A -15V/1A
SRW-100-3003 +5V/10A(2) +3.3V/8A -12V/1A
SRW-100-3004 +3.3V/10A +5.8V/3A -48V/1A
SRW-100-2001 +12V/5A -12V/4A
SRW-100-2002 +15V/5A -15V/3A
SRW-100-2003 +12.5V/4A +16V/2A
SRW-100-1001 3.3V/20A(4)
SRW-100-1002 5V/20A
SRW-100-1003 12V/8.3A
SRW-100-1004 15V/6.7A
SRW-100-1005 24V/4.2A
SRW-100-1006 28V/3.6A
SRW-100-1007 48V/2.1A
SRW-100-1008 40V/2.5A
SRP-100-4001 +5V/12A(2) +24V/3A +12V/2A (3) -12V/1A
SRP-100-4002 +5V/12A(2) +24V/3A +15V/2A (3) -15V/1A
SPR-100-4003 +5V/12A(2) -5V/4A +12V/2A (3) -12V/1A
SRP-100-4004 +5V/12A(2) -5V/4A +15V/2A (3) -15V/1A
SRP-100-4005 +5V/12A +12V/3A +8V/2A -8V/1A
SRP-100-3001 +5V/12A(2) +12V/4A -12V/1A
SRP-100-2001 +5V/12A(2) +24V/3A
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
Notes
Consult factory for alternate output configurations.
Consult factory for positive, negative or floating outputs. Refer to Application Information for complete
output power ratings.
All specifications are maximum at 25o C unless otherwise stated and are subjected to change without
notice. Specify optional perforated cover, power fail, overvoltage protection, isolated output 2, isolated
output 4 or DC Input when ordering.
SAFETY SPECIFICATIONS
General Protection Class: I
Overvoltage Category: II
Pollution Degree: 2
Underwriters UL 60950, Third Edition
Laboratories UL 2601 - 1 Second Edition
File E137708 CB Report Per IEC 950 (1991)
Second Edition A1, A2, A3, A4
All EN 60950 Deviations
CB Report Per IEC 601-1-(1988)
First Edition, A1, A2
UL Recognition Mark for CAN/CSA-C22.2 No. 60950:00
Canada CAN/CSA-C22.2 No. 601-1-M90
File E137708
TUV EN 60950:2000
EN 60601-1/A2: 1995
Low Voltage Directive
SRW/SRP-100 SERIES MECHANICAL SPECIFICATIONS
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de
APPLICATIONS INFORMATION
1. Each output can deliver its rated current but 17. This product was type tested and safety
total output power must not exceed 70, 85 or certificated using the the dielectric
100 watts as determined by cooling method. strength test voltages listed in Table V
2. Rated 8A with convection cooling. of UL 60601-1. In consideration of clause
3. Rated 1A with convection cooling. 20.4g, care must be taken to insure the
4. Rated 50 watts maximum output power when voltage applied to a reinforced insulation
does not over stress basic insulation.
convection cooled, 70 watts when baseplate or
Secondary to ground capacitors may
forced air cooled.
need to be removed prior to performing
5. Free air convection cooling, 70 watts maximum
a dielectric strength type test on the
output power.
end product. It is highly recommended
6. Base plate cooling rating of 85 watts requires a that the DC test voltages listed in DVB.1.
one square foot.09 thick aluminium area Annex DVB are not exceeded during
attached to bottom four mounting holes. a production-line dielectric strength
7. Forced air cooling rating of 100 watts requires test of the assembled end product.
an air speed of 200 linear feet per minute Please consult factory for
flowing past a point one inch above the main further information.
isolation transformer.
8. Semiconductor case temperatures must not Maximum Output Power vs. Ambient
exceed 110o C. Temperature
9. Sufficient area must be provided around the
convection cooled power supplies to allow
natural movement of air to develop.
10. This product is intended for use as
professionally installed component within
information technology and medical equipment.
11. A minimum load of 10% is required on output
one to ensure proper regulation of remaining
outputs.
12. Remote sense terminals may be used to
compensate for cable losses up to 250mV. The
use of twisted pair is recommended as well as a CONNECTOR SPECIFICATIONS
decoupling capacitor (0.1-10ÂHF) and a Terminal block with 4-40
capacitor of 100ÂHF /amp connected across the P1 AC Input screws on 0.325 inch centers
load side. (Single) mates with #4 spade
13. Peak to peak output ripple and noise is terminals.
measured directly at the output .156 friction lock header
terminals of the power supply, without the use mates with Molex 09-50-3031
of the probe ground lead or retractable tip, 20 P1 AC Input or equivalent crimp terminal
MHz bandwidth. (Multiple) housing with Molex
14. This product includes only one fuse in the input 08-50-0189 or equivalent
circuit. In consideration of Clause 57.6 of UL crimp terminal.
2601-1, a second fuse may be required in the 6-32 screw down terminal
P2 DC Output(Single) mates with #6 ring tongue
end product.
terminal.(10 in-lb max.)
15. This power supply has been safety approved
.156 friction lock header
and final tested using a DC dielectric strength
mates with Molex 09-50-3101
test. Please consult factory before performing
or equivalent crimp terminal
an AC dielectric strength test. P2 DC Output(Multiple)
housing with Molex
16. Maximum screw penetration into chassis 08-50-0189 or equivalent
mounting holes is .125 inches. crimp terminal.
.187 quick disconnect
RECOMMENDED AIR FLOW DIRECTION G Ground
terminal.
1.Optimum 2.Good 3.Fair .100 friction lock header
mates with Molex 22-55-2047
P3 P.F./Sense(Single) or equivalent crimp terminal
housing with Molex 6459 or
equivalent crimp terminal.
.100 friction lock header
P.F./Sense(Multiple) mates with Molex 50-57-2027
P3 or equivalent crimp terminal
housing with Molex 6459 or
equivalent crimp terminal.
CompuMess Elektronik GmbH · Lise-Meitner-Str.1 · 85716 Unterschleissheim
Tel 089-321501-0 · Fax 089-321501-11 · www.compumess.de · www.netzteile.de