Hier Klicken für das PDF Dokument!!!
65 WATTS
NO MINIMUM ORDER REQUIRED
SRW-65 SERIES OUTPUT SPECIFICATIONS
Features Total Output Power at 65 W
500 C
RoHS Output Voltage Output 1: +/-1.0%
Universal 85-264 VAC Input Centering Output 2: +/-5.0%
Compact 4.0" X 6.0" X 1.1" Size Output 3: +/-5.0%
Output 4: +/-5.0%
Class B Emissions Per EN 55022
(All outputs at 50% load )
2 Year Warranty Source Regulation Outputs 1-4: 0.5%
Fits 1U Application Load Regulation Output 1: 1.0% (10-100%Load
EN 60950-1 ITE Certification Change)
One to Four Outputs Output 2: 5.0% (20-80% Load
Change)
Optional Chassis & Cover Output 3: 5.0% (20-80% Load
Change)
Output 4: 5.0% (20-80% Load
Change)
Cross Regulation Output 2: 5.0%
Output 3: 5.0%
Output 4: 5.0%
(Output 1 load varied 50-100%)
Output Voltage AdjustOutput 1: 95% to 105%
Range
Output Noise Outputs 1-4: 1.0%
Turn On Overshoot None
Transient Response Outputs 1-4
Volt. Deviation 5.0%
Recovery Time 2 mS
Load Change 50% To 100%
Output Overvoltage Output 1: 110% to 150%
Protection (Optional)
Output Overpower Output 1-4 110% Min.
Protection Outputs cycle on/off, auto recovery
Hold Up Time 16 mS Min, 65 W Output
120 V Inputt
Start Up Time 1 Second
INPUT SPECIFICATIONS ENVIRONMENTAL SPECIFICATIONS
Source Voltage 85-264 Voltage AC Ambient Operating 0 oC to +70oC Derating:
Frequency Range 47-63 Hz Temperature Range See Power Rating Chart
Source Current Ambient Storage
True RMS 1.5A At 85V Inputut -40 oC to +85oC
Temperature Range
Peak Inrush 40A
Temperature Coefficient Outputs 1-4: 0.02%/oC
Efficiency .72 -.80 (Varies by model)
Conducted Emissions EN 55022 Class B
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
Ph: 570-824-4666 Fx: 570-824-4843info@compumess.de · www.compumess.de · www.netzteile.de
SAFETY SPECIFICATIONS GENERAL SPECIFICATIONS
General Protection Class: I Dielectric Strength
Reinforced Insulation 4242 VDC, Primary to
Overvoltage Category: II Secondary, 1 Sec.
Basic Insulation 2121 VDC, Primary to
Ground, 1 Sec.
Pollution Degree: 2 Operational Insulation 500 VDC, Secondary to
Ground, 1 Sec
Underwriters UL 60950-1 First Edition
Laboratories Mean Time Between 150,000 Hours min.,
File E137708
Failures MIL-HDBK-217F, 25oC, GB
UL Recognition CAN/CSA-C22.2 No. Weight 1.65 Lbs. Chassis and Cover
Mark for 60950-1-03 0.80 Lbs. Open Frame
Canada
File E137708 Logic low with input power
TUV EN 60950-1:2001 failure, 2mS minimum prior
Power Fail Signal
(Optional) to output 1 dropping 1%
Low Voltage Directive
CB Report per IEC
60950-1(2001) First
Edition All National
Deviations
MODEL LISTING
Model Output 1 Output 2 Output 3 Output 4
SRW-65-4001 +5V/5A -5V/3A +12V/2A -12V/2A
SRW-65-4002 +5V/5A +12V/1A +12V/2A -12V/2A
SRW-65-4003 +5V/5A +24V/1A +12V/2A -12V/2A
SRW-65-4004 +5V/5A -5V/3A +15V/2A -15V/2A
SRW-65-4005 +5V/5A +24V/1A +12V/2A -5V/2A
SRW-65-4006 +5V/5A +24V/1A +15V/2A -15V/2A
SRW-65-4007 +5V/5A +26V/1A +15V/2A -15V/2A
SRW-65-4008 +5V/5A +24V/1A +12V/2A -12V/2A
SRW-65-4009 +5V/7.5A +48V/.25A +15V/1A -15V/1A
SRW-65-4103 +5V/5A 26V/1A +12V/2A -12V/2A
SRW-65-4104 +5V/4A 5V/.25A +15V/2.5A 24V/.5A
SRW-65-3001 +5V/5A +12V/3A -12V/1A
SRW-65-3002 +5V/7A +12V/2A -12V/2A
SRW-65-3003 +5V/7A +15V/2A -15V/2A
SRW-65-3004 +5V/5A -5V/4A +12V/2A
SRW-65-3005 +5V/5A -5V/4A +24V/1A
SRW-65-3006 +5.25V/6A +15V/1A +34V/1.5A
SRW-65-2001 +5V/7A -5V/5A
SRW-65-2002 +5V/7A +12V/3A
SRW-65-2003 +12V/3A -12V/2.5A
SRW-65-2004 +15V/2.5A -15V/2A
SRW-65-2005 +5V/7A +24V/1.5A
SRW-65-2006 +5V/9A +12V/2A
SRW-65-2008 +6V/5A -6V/5A
SRW-65-1001 5V/13A
SRW-65-1002 12V/5.4A
SRW-65-1003 15V/4.3A
SRW-65-1004 24V/2.7A
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
Ph: 570-824-4666 Fx: 570-824-4843info@compumess.de · www.compumess.de · www.netzteile.de
SRW-65-1005 18V/3.6A
SRW-65-1006 24V/3.33A
SRW-65-1104 24V/3.33A
SRW-65-1105 21V/3.1A
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
Ph: 570-824-4666 Fx: 570-824-4843info@compumess.de · www.compumess.de · www.netzteile.de
Notes
Consult factory for alternate output configuration.
Consult factory for positive, negative or floating outputs.
Refer to Application Information for complete output power ratings.
All specifications are maximum at 25C unless otherwise stated and are subjected to change without
notice.
Specify optional chassis and cover, power fail, overvoltage protection, transient protection or DC Input
when ordering.
TUV only:SRW-65-2008
SRW-65 SERIES MECHANICAL SPECIFICATIONS
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
Ph: 570-824-4666 Fx: 570-824-4843info@compumess.de · www.compumess.de · www.netzteile.de
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
Ph: 570-824-4666 Fx: 570-824-4843info@compumess.de · www.compumess.de · www.netzteile.de
APPLICATIONS INFORMATION
1. Each output can deliver its rated 8. This power supply has been safety approved and final
current but total output power must tested using a DC
not exceed dielectric strength test. Please consult factory before
65 watts. performing AC dielectric strength test.
2. Semiconductor case temperature 9. Maximum screw penetration into mounting holes is .250
must not exceed 110 C inches
3. Sufficient area must be provided
around convection cooled power Maximum Output Power vs. Ambient Temperature
supplies to allow natural movement
of air develop.
4. This product is intended for use as a
professionally installed component
within information technology and
medical equipment.
5. A minimum load of 20% is required
on output one to insure proper
regulation of remaining outputs.
6. Peak to peak output ripple and
noise is measured directly at the
output
terminals of the power supply,
without the use of the probe ground
lead or retractable tip, 20 MHz
bandwidth.
This product was type tested and CONNECTOR SPECIFICATIONS
7.
safety certificated using the the .156 friction lock header mates with Molex
AC
dielectric strength test voltages TB1 09-50-3051 or equivalent crimp terminal housing
Input
listed in Table 5B of UL 60950-1. In with Molex 08-50-0189 or equivalent crimp terminal.
consideration of clause 5.2.2, care .156 friction lock header mates with Molex
DC
must be taken to insure the voltage TB2Output 09-50-3101 or equivalent crimp terminal housing
applied to a reinforced insulation with Molex 08-50-0189 or equivalent crimp terminal.
does not over stress basic PF Optional power fail signal.
insulation. Secondary to ground G Optional power fail signal return.
capacitors may need to be removed RECOMMENDED AIR FLOW DIRECTION
prior to performing a dielectric 1. Optimum
strength type test on the end 2. Good
product. It is highly recommended 3. Fair
that the DC test voltages be used
when performing a production-line
dielectric strength test of the
assembled end product. Please
consult factory for further
information.
CompuMess Elektronik GmbH · Lise-Meitner-Str. 1 · D-85716 Unterschleißheim
Telefon (089) 32 15 01 - 0 · Telefax (089) 32 15 01 - 11
Ph: 570-824-4666 Fx: 570-824-4843info@compumess.de · www.compumess.de · www.netzteile.de